9.6
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Event Reports and SER
Standard 15-, 30-, or 60-Cycle Event Reports
XFMR 1 Date: 02/28/97 Time: 06:28:38.888
STATION A
FID=SEL-387-R102-V#####-D970226
Winding 1 Winding 2 Winding 3 Winding 4 OUT IN
Amps Sec Amps Sec Amps Sec Amps Sec 1357 135
IAW1 IBW1 ICW1 IAW2 IBW2 ICW2 IAW3 IBW3 ICW3 IAW4 IBW4 ICW4 246A 246
[1]
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
[2]
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234>.... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234*.... ...
.
.
.
[15]
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
+1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 +1234 .... ...
Event: TRIP1 TRIP2 TRIP3 TRIP4 TRIP5
Targets: TRIP INST 87-1 87-2 87-3 50 51 A B C N W1 W2 W3 W4
Winding 1 Currents (A Sec), ABC: 123.4 123.4 123.4
Winding 2 Currents (A Sec), ABC: 123.4 123.4 123.4
Winding 3 Currents (A Sec), ABC: 123.4 123.4 123.4
Winding 4 Currents (A Sec), ABC: 123.4 123.4 123.4
Figure 9.2
Example Winding Event Report
The trigger row includes a
>
character following immediately after the last
analog column to indicate the trigger point. A
*
character following
immediately after the last analog column denotes that the designated row was
used for the Event Summary currents. The
*
character takes precedence over
the
>
character when both conditions occur for the same row.
summarizes the event report current columns. The column headings
shown are the default headings, corresponding to the designations on
terminals
Z01
to
Z24
. If the Analog Input Labels settings have been changed
within the Global setting area, these will appear in the report as set.
summarizes the winding event report output and input columns.
Table 9.2
Winding Event Report Current Columns
Column
Heading
Definition
IAW1
Current measured by Winding 1 input channel IA (Amps, secondary)
IBW1
Current measured by Winding 1 input channel IB (Amps, secondary)
ICW1
Current measured by Winding 1 input channel IC (Amps, secondary)
IAW2
Current measured by Winding 2 input channel IA (Amps, secondary)
IBW2
Current measured by Winding 2 input channel IB (Amps, secondary)
ICW2
Current measured by Winding 2 input channel IC (Amps, secondary)
IAW3
Current measured by Winding 3 input channel IA (Amps, secondary)
IBW3
Current measured by Winding 3 input channel IB (Amps, secondary)
ICW3
Current measured by Winding 3 input channel IC (Amps, secondary)
IAW4
Current measured by Winding 4 input channel IA (Amps, secondary)
IBW4
Current measured by Winding 4 input channel IB (Amps, secondary)
ICW4
Current measured by Winding 4 input channel IC (Amps, secondary)
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...