F-2
Setting Negative-Sequence Overcurrent Elements
Date Code 990215
SEL-351P Manual Técnico
To avoid having negative-sequence time-overcurrent element 51QT with such low time-dial
settings trip for this transient negative-sequence current condition, make corresponding minimum
response time setting:
51QMR = 1.50 cycles
(minimum response time; transient condition lasts
less than 1.5 cycles)
Figure APPENDIX F: .1:
Minimum Response Time Added to a
Negative-Sequence Time-Overcurrent Element 51QT
Continue reading in
Coordinating Negative-Sequence Overcurrent Elements
in this appendix
for guidelines on coordinating negative-sequence time-overcurrent elements and a following
coordination example.
C
OORDINATING
N
EGATIVE
-S
EQUENCE
O
VERCURRENT
E
LEMENTS
The following coordination guidelines and example assume that the negative-sequence
overcurrent elements operate on 3I
2
magnitude negative-sequence current and that the power
system is radial. The negative-sequence overcurrent elements in the SEL
-
351P Recloser Control
operate on 3I
2
magnitude negative-sequence current.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......