Date Code 990430
Serial Port Communications and Commands
10-47
SEL-351P Manual Técnico
E:DAKOTA
B:EDITH
2:TAIL
=>>
The above listings are the
factory default passwords
for Access Levels 1, E, B, and 2. To
change the password for Access Level 1 to BIKE, enter the following:
=>>PAS 1 BIKE <ENTER>
Set
=>>
After entering new passwords, type
PAS <ENTER>
to inspect them. Make sure they are what
you intended, and record the new passwords.
Passwords may include up to six characters. Valid characters consist of: ‘A - Z’, ‘a - z’, ‘0 - 9’,
‘-’, and ‘.’. Upper- and lower-case letters are treated as different characters. Examples of valid,
distinct passwords include:
OTTER otter Ot3456 TAIL 123456 12345. 12345-
If the passwords are lost or you wish to operate the recloser control without password protection,
put the main board Password jumper in place (Password jumper = ON). Refer to Table 2.4 and
Table 2.5 for Password jumper information.
If you wish to disable password protection for a specific access level [even if Password jumper is
not in place (Password jumper = OFF)], simply set the password to DISABLE. For example
PAS 1 DISABLE
disables password protection for Level 1.
SET Command (Change Settings)
Use the SET command to change “regular” settings, EZ recloser control settings, global settings,
SEL
OGIC
Control Equations settings, serial port settings, sequential events recorder (SER)
settings, and text label settings. Below are the SET command options.
SET n
Change “regular” settings for settings group
n
.
n
specifies
the settings group (1, 2, 3, 4, 5, or 6);
n
defaults to the
active settings group if not listed.
SET EZ n
Change EZ recloser control settings for settings group
n
.
n
specifies the settings group (1, 2, 3, 4, 5, or 6);
n
defaults to the active settings group if not listed. See
additional information in subsection
Access Level E (EZ)
Commands
.
SET FZ
Change EZ global settings. See additional information in
subsection
Access Level E (EZ) Commands
.
SET G
Change global settings.
SET L n
Change SEL
OGIC
Control Equation settings for settings
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......