Date Code 990215
Breaker/Recloser Monitor, Battery System Monitor,
8-25
Metering, and Load Profile Functions
SEL-351P Manual Técnico
Time = 10 Minutes
The three 5-minute intervals in the sliding time-window at “Time = 10 minutes” each integrate
into the following 5-minute totals:
5-Minute Totals
Corresponding
5-Minute Interval
0.0 per unit
-5 to 0 minutes
1.0 per unit
0 to 5 minutes
1.0 per unit
5 to 10 minutes
2.0 per unit
Rolling demand meter response at “Time = 10 minutes” = 2.0/3 = 0.67 per unit
Time = 15 Minutes
The three 5-minute intervals in the sliding time-window at “Time = 15 minutes” each integrate
into the following 5-minute totals:
5-Minute Totals
Corresponding
5-Minute Interval
1.0 per unit
0 to 5 minutes
1.0 per unit
5 to 10 minutes
1.0 per unit
10 to 15 minutes
3.0 per unit
Rolling demand meter response at “Time = 15 minutes” = 3.0/3 = 1.0 per unit
Demand Meter Settings
Table SECTION 8: .5: Demand Meter Settings and Settings Range
Setting Definition
Range
EDEM
Demand meter type
THM = thermal
ROL = rolling
DMTC
Demand meter time constant
5, 10, 15, 30, or 60 minutes
PDEMP
Phase demand current pickup
OFF
NDEMP*
Neutral ground demand current pickup
0.20 - 6.40 A (1 A nominal)
GDEMP
Residual ground demand current pickup
in 0.01 A steps
QDEMP
Negative-sequence demand current pickup
*0.005 - 0.20A (0.05 A nominal channel IN current input)
Note
: Changing setting EDEM or DMTC resets the demand meter values to zero. This also
applies to changing the active setting group, and setting EDEM or DMTC is different in
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......