Date Code 990430
Breaker/Recloser Monitor, Battery System Monitor,
8-11
Metering, and Load Profile Functions
SEL-351P Manual Técnico
50% to 100% Breaker Wear
Refer to Figure SECTION 8: .7. The current value changes from 12.0 kA to 1.5 kA. 1.5 kA is
interrupted 3000 times (3000 close/open operations = 6000 - 3000), pushing the breaker
maintenance curve from the 50% wear level to the 100% wear level.
When the breaker maintenance curve reaches 100% for a particular phase, the percentage wear
remains at 100% (even if additional current is interrupted) until reset by the BRE R command
(see
View or Reset Breaker Monitor Information
that follows later). But the current and trip
counts continue to be accumulated until reset by the BRE R command.
Additionally, logic outputs assert for alarm or other control applications – see the following
discussion.
Breaker Monitor Output
When the breaker maintenance curve for a particular phase (A, B, or C) reaches the 100% wear
level (see Figure SECTION 8: .7), a corresponding Relay Word bit (BCWA, BCWB, or BCWC)
asserts.
Relay Word bit Definition
BCWA
Phase A breaker contact wear has reached the 100% wear level
BCWB
Phase B breaker contact wear has reached the 100% wear level
BCWC
Phase C breaker contact wear has reached the 100% wear level
BCW
BCWA + BCWB + BCWC
Example Applications
These logic outputs can be used to alarm:
OUT105 = BCW
or drive the relay to lockout the next time the relay trips:
79DTL = … + TRIP * BCW
View or Reset Breaker Monitor Information – Including Trip Operation Counters
Accumulated breaker wear/operations data are retained if the relay loses power or the breaker
monitor is disabled (setting EBMON = N). The accumulated data can only be reset if the BRE R
command is executed (see the following discussion on the BRE R command).
Via Serial Port
See
BRE Command (Breaker Monitor Data)
in
Section 10: Serial Port Communications and
Commands
. The BRE A command displays the following information:
•
Accumulated number of recloser control initiated trips
•
Accumulated interrupted current from recloser control initiated trips
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......