3-48
Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Date Code 990430
SEL-351P Manual Técnico
Table SECTION 3: .10: Frequency Elements Settings and Settings Ranges
Setting Definition
Range
27B81P
undervoltage frequency element block
20.0 - 150.0 V secondary
81D1P
frequency element 1 pickup
40.10 - 65.00 Hz
81D1D
frequency element 1 time delay
2.00 - 16000.00 cycles, in
0.25-cycle steps
81D2P
frequency element 2 pickup
40.10 - 65.00 Hz
81D2D
frequency element 2 time delay
2.00 - 16000.00 cycles, in
0.25-cycle steps
81D3P
frequency element 3 pickup
40.10 - 65.00 Hz
81D3D
frequency element 3 time delay
2.00 - 16000.00 cycles, in
0.25-cycle steps
81D4P
frequency element 4 pickup
40.10 - 65.00 Hz
81D4D
frequency element 4 time delay
2.00 - 16000.00 cycles, in
0.25-cycle steps
81D5P
frequency element 5 pickup
40.10 - 65.00 Hz
81D5D
frequency element 5 time delay
2.00 - 16000.00 cycles, in
0.25-cycle steps
81D6P
frequency element 6 pickup
40.10 - 65.00 Hz
81D6D
frequency element 6 time delay
2.00 - 16000.00 cycles, in
0.25-cycle steps
Accuracy
Pickup:
±
0.01 Hz
Timer:
±
0.25 cycles and
±
0.1% of setting
Create Over- and Underfrequency Elements
Refer to Figure SECTION 3: .28.
Note that pickup settings 81D1P through 81D6P are compared to setting NFREQ. NFREQ is the
nominal frequency setting (a global setting), set to 50 or 60 Hz.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......