1-50
Factory-Set Logic
Date Code 990215
SEL-351P Manual Técnico
SEL
OGIC
settings
SET3
(set)
(reset)
Relay
Word
Bits
PB3
Relay
Word
Bit
LT3
RST3
DWG: MP351P029
REMOTO
HABILITADO
operator control
pushbutton
(pulsed output - see
Figure 1.33)
LT3 is not used in any
factory-set logic. User
needs to program particular
SELogic settings to realize
the desired hierarchy in
local/remote control. See
Figure 1.40)
BLOQUEIO operator
control OFF (see
Figure 1.44)
LT4
REMOTO
HABILITADO
operator control ON
(LT3 = logical 1)
Figure SECTION 1: .39:
REMOTO HABILITADO Operator Control Logic
Application
Example Application for the REMOTO HABILITADO Operator Control
To use the REMOTO HABILITADO operator control, change the corresponding LED setting to
LED3 = LT3 (to monitor the output of latch LT3) and assign LT3 to a supervising role in logic.
For example, Figure SECTION 1: .40 is a logic modification to Figure SECTION 1: .37
(TERRA HABILITADO operator control). Latch LT1 can be set/reset locally (with TERRA
HABILITADO operator control pushbutton) or remotely (with input IN101). Note that the
remote control (IN101) is supervised by Relay Word bit LT3 (REMOTO HABILITADO
operator control). Likewise, the local control (TERRA HABILITADO operator control) is
supervised by Relay Word bit LT4 (BLOQUEIO operator control). This is just one example –
many variations are possible.
SEL
OGIC
settings
SET1
(set)
(reset)
Relay
Word
Bit
LT1
RST1
DWG: MP351P030
TERRA
HABILITADO
operator
control LED
setting
LED1 = LT1
LT1 is used in the
following SEL
OGIC
settings to enable/
disable ground
overcurrent elements:
67N1TC
67N2TC
67N3TC
51N1TC
51N2TC
torque control equations
for neutral ground
overcurrent elements
67G1TC
67G2TC
51G1TC
51G2TC
torque control equations
for residual ground
overcurrent elements
IN101
Input IN101 pulsed by
SCADA contact to
enable/disable ground
overcurrent protection
LT3
REMOTO
HABILITADO
operator control ON
(see Figure 1.43)
Relay
Word
Bits
PB1
TERRA
HABILITADO
operator control
pushbutton
(pulsed output - see
Figure 1.33)
Rising
edge
detect
LT4
BLOQUEIO operator
control OFF (see
Figure 1.44)
TERRA HABILITADO
operator control ON (by
local or remote means;
LT1 = logical 1)
Local
Remote
Figure SECTION 1: .40:
Example REMOTO HABILITADO Operator Control
Application (supervising remote control of ground overcurrent elements)
SEF HABILITADO Operator Control
Figure SECTION 1: .41 describes the logic driven by the SEF HABILITADO operator control
pushbutton (pulsed output PB6) and operation of the corresponding LED. Note that the
BLOQUEIO operator control logic supervises the SEF HABILITADO operator control. The
BLOQUEIO operator control has to be OFF (LT4 = logical 1) in order for the SEF
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......