programmed in the SER report, the change is detected as the receipt of an SER
record (which contains the SER timestamp) within the relay.
For all other Booleans or Bstrings, the change is detected via the scanner,
which compares the last state against the previous state to detect the change.
For analogs, the scanner looks at the amount of change relative to the
deadband configured for the point to indicate a change and apply the
timestamp. In all cases, these timestamps are used for the reporting model.
Functionally Constrained Data Attributes mapped to points assigned to the
SER report have 4 ms SER-accurate timestamps for data change events. In
order to ensure that you will get SER-quality timestamps for changes to
certain points, you must include those points in the SER report. All other
FCDAs are scanned for data changes on a 1/2-second interval and have 1/2-
second timestamp accuracy. See the
SET R
command for information on
programming the SER report.
The SEL-787 uses GOOSE quality attributes to indicate the quality of the data
in its transmitted GOOSE messages. Under normal conditions, all attributes
are zero, indicating good quality data.
shows the GOOSE quality
attributes available to devices that subscribe to GOOSE messages from
SEL-787 datasets that contain them. Internal status indicators provide the
information necessary for the device to set these attributes. For example, if the
device becomes disabled, as shown via status indications (e.g., an internal
self-test failure), the SEL-787 will set the Validity attribute to invalid and the
Failure attribute to TRUE. Note that the SEL-787 does not set any of the other
quality attributes. These attributes will always indicate FALSE (0). See the
AC
SEL
ERATOR
Architect online help for additional information on GOOSE
Quality attributes.
Figure F.3
Goose Quality
GOOSE Processing
SEL devices support GOOSE processing as defined by IEC 61850-7-1:2003(E),
IEC 61850-7-2:2003(E), and IEC 61850-8-1:2004(E) via the installed
Ethernet port. Outgoing GOOSE messages are processed in accordance with
the following constraints:
➤
The user can define up to eight outgoing GOOSE messages
consisting of any Data Attribute (DA) from any Logical Node.
A single DA can be mapped to one or more outgoing GOOSE,
or one or more times within the same outgoing GOOSE. A user
can also map a single GOOSE dataset to multiple GOOSE
control blocks.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...