IEC 61850 Communications
IEC 61850 Operation
Unlike other Supervisory Control and Data Acquisition (SCADA) protocols
that present data as a list of addresses or indices, IEC 61850 presents data with
descriptors in a composite notation made up of components.
shows
how the Winding 1A-phase current expressed as MMXU$A1$phsA$cVal is
broken down into its component parts.
Data Mapping
Device data is mapped to IEC 61850 Logical Nodes (LN) according to rules
defined by SEL. Refer to IEC 61850-5:2003(E) and IEC 61850-7-4:2003(E)
for the mandatory content and usage of these LNs. The SEL-787 Logical
Nodes are grouped under Logical Devices for organization based on function.
See
for descriptions of the Logical Devices in an SEL-787. See
for a description of the LNs that make up these Logical
Devices.
MMS
Manufacturing Messaging Specification (MMS) provides services for the
application-layer transfer of real-time data within a substation LAN. MMS
was developed as a network independent data exchange protocol for industrial
networks in the 1980s and standardized as ISO 9506.
In theory, you can map IEC 61850 to any protocol. However, it can be
unwieldy and quite complicated to map objects and services to a protocol that
only provides access to simple data points via registers or index numbers.
MMS supports complex named objects and flexible services that enable
mapping to IEC 61850 in a straightforward manner. This was why the UCA
users group used MMS for UCA from that start, and why the IEC chose to
keep it for IEC 61850.
GOOSE
The Generic Object Oriented Substation Event (GOOSE) object within IEC
61850 is for high-speed control messaging. IEC 61850 GOOSE automatically
broadcasts messages containing status, controls, and measured values onto the
network for use by other devices. IEC 61850 GOOSE sends the messages
several times, increasing the likelihood that other devices receive the
messages.
IEC 61850 GOOSE objects can quickly and conveniently transfer status,
controls, and measured values between peers on an IEC 61850 network.
Table F.2
Example IEC 61850 Descriptor Components
Components
Description
MMXU
Logical Node
Polyphase measurement unit
A1
Data Object
Phase-to-ground amperes, Winding 1
PhsA
Sub-Data Object
Phase A
cVal
Data Attribute
Complex value
Table F.3
SEL-787 Logical Devices
Logical Device
Description
ANN
Annunciator elements—alarms, status values
CFG
Configuration elements—datasets and report control blocks
CON
Control elements—Remote bits
MET
Metering or Measurement elements—currents, voltages, power, etc.
PRO
Protection elements—protection functions and breaker control
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...