7.22
SEL-787 Relay
Instruction Manual
Date Code 20081022
Communications
SEL ASCII Protocol and Commands
An example response to the
GOOSE
commands is shown in
.
#>
GOOSE <Enter>
GOOSE Transmit Status
MultiCastAddr Ptag:Vlan StNum SqNum TTL Code
-----------------------------------------------------------------------------
SEL_787_2CFG/LLN0$GO$GooseDSet13
01-0C-CD-01-00-04 4:1 2 20376 50
Data Set: SEL_787_2CFG/LLN0$DSet13
GOOSE Receive Status
MultiCastAddr Ptag:Vlan StNum SqNum TTL Code
-----------------------------------------------------------------------------
SEL_787_1CFG/LLN0$GO$NewGOOSEMessage5
01-0C-CD-01-00-05 4:0 1 100425 160
Data Set: SEL_787_1CFG/LLN0$DSet10
SEL_787_1CFG/LLN0$GO$NewGOOSEMessage3
01-0C-CD-01-00-03 4:0 1 98531 120
Data Set: SEL_787_1CFG/LLN0$DSet05
SEL_787_1CFG/LLN0$GO$NewGOOSEMessage2
01-0C-CD-01-00-02 4:0 1 97486 200
Data Set: SEL_787_1CFG/LLN0$DSet04
SEL_787_1CFG/LLN0$GO$NewGOOSEMessage1
01-0C-CD-01-00-01 4:0 1 96412 190
Data Set: SEL_787_1CFG/LLN0$DSet03
SEL_387E_1CFG/LLN0$GO$NewGOOSEMessage5
01-0C-CD-01-00-06 4:0 1 116156 140
Data Set: SEL_387E_1CFG/LLN0$DSet10
SEL_387E_1CFG/LLN0$GO$NewGOOSEMessage4
01-0C-CD-01-00-05 4:0 1 116041 130
Data Set: SEL_387E_1CFG/LLN0$DSet06
SEL_387E_1CFG/LLN0$GO$NewGOOSEMessage2
01-0C-CD-01-00-02 4:0 1 115848 120
Data Set: SEL_387E_1CFG/LLN0$DSet04
SEL_387E_1CFG/LLN0$GO$NewGOOSEMessage1
01-0C-CD-01-00-01 4:0 1 115798 150
Data Set: SEL_387E_1CFG/LLN0$DSet03
=>
Figure 7.10
GOOSE Command Response
GROUP Command
Use the
GROUP
) to display the active settings
group or try to force an active settings group change.
When you change the active group, the relay responds with a confirmation
prompt:
Are you sure (Y/N)?
Answer
Y <Enter>
to change the active
group. The relay asserts the Relay Word bit SALARM for one second when
you change the active group.
If any of the SEL
OGIC
control equations SS1–SS3 are set when you issue the
GROUP
n
command, the group change will fail. The relay responds:
Command
Unavailable: Active setting group SEL
OGIC
equations have priority
over the GROUP command
.
Table 7.19
GROUP Command
Command
Description
Access Level
GROUP
Display the active settings group.
1
GROUP
n
a
a
Parameter n indicates group numbers 1–4.
Change the active group to Group
n
.
2
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...