SEL-787 Relay
Instruction Manual
Date Code 20081022
Protection and Logic Functions
Global Settings (SET G Command)
=>>
SET G AI301NAM TERSE <Enter>
Global
AI 301 Settings
AI301 TAG NAME (8 characters)
AI301NAM:= AI301
?
TX_TEMP <Enter>
AI301 TYPE (I,V) AI301TYP:= I ?
<Enter>
AI301 LOW IN VAL (-20.480 to 20.480 mA) AI301L := 4.000 ?
<Enter>
AI301 HI IN VAL (-20.480 to 20.480 mA) AI301H := 20.000 ?
<Enter>
AI301 ENG UNITS (16 characters)
AI301EU := mA
?
degrees C
<Enter>
AI301 EU LOW (-99999.000 to 99999.000) AI301EL := 4.000 ?
-50 <Enter>
AI301 EU HI (-99999.000 to 99999.000) AI301EH := 20.000 ?
150 <Enter>
AI301 LO WARN L1 (OFF,-99999.000 to 99999.000) AI301LW1:= OFF ?
<Enter>
AI301 LO WARN L2 (OFF,-99999.000 to 99999.000) AI301LW2:= OFF ?
<Enter>
AI301 LO ALARM (OFF,-99999.000 to 99999.000) AI301LAL:= OFF ?
<Enter>
AI301 HI WARN L1 (OFF,-99999.000 to 99999.000) AI301HW1:= OFF ?
65 <Enter>
AI301 HI WARN L2 (OFF,-99999.000 to 99999.000) AI301HW2:= OFF ?
95 <Enter>
AI301 HI ALARM (OFF,-99999.000 to 99999.000) AI301HAL:= OFF ?
115 <Enter>
AI 302 Settings
AI302 TAG NAME (8 characters)
AI302NAM:= AI302
?
END <Enter>
Save changes (Y,N)? Y
<Enter>
Settings Saved
=>>
Figure 4.56
Settings to Configure Input 1 as a 4–20 mA Transducer
Measuring Temperatures Between -50°C and 150°C
Analog (DC Transducer) Input Board
shows the setting prompt, setting range, and factory default settings
for an analog input card in Slot
3
. For the name setting (AI301NAM, for
example), enter only alphanumeric and underscore characters. Characters are
not case sensitive, but the device converts all lowercase characters to
uppercase. Although the device accepts alphanumeric characters, the name
AI301NAM setting must begin with an alpha character (A–Z) and not a
number.
Table 4.37
Analog Input Card in Slot 3
Setting Prompt
Setting Range
Setting Name :=
Factory Default
AI301 TAG NAME
8 characters 0–9, A–Z, _
AI301NAM := AI301
AI301 TYPE
I, V
AI301TYP := I
AI301 LOW IN VAL
–20.480 to +20.480 mA
AI301L := 4.000
AI301 HI IN VAL
–20.480 to +20.480 mA
AI301H := 20.000
AI301 LOW IN VAL
–10.240 to +10.240 V
AI301L := 0.000
a
a
Voltage setting range for a voltage transducer, i.e., when AI301TYP := V.
AI301 HI IN VAL
–10.240 to +10.240 V
AI301H := 10.000
AI301 ENG UNITS
16 characters
AI301EU := mA
AI301 EU LOW
–99999.000 to +99999.000
AI301EL := 4.000
AI301 EU HI
–99999.000 to +99999.000
AI301EH := 20.000
AI301 LO WARN 1
OFF, –99999.000 to +99999.000
AI301LW1 := OFF
AI301 LO WARN 2
OFF, –99999.000 to +99999.000
AI301LW1 := OFF
AI301 LO ALARM
OFF, –99999.000 to +99999.000
AI301LAL := OFF
AI301 HI WARN 1
OFF, –99999.000 to +99999.000
AI301HW1 := OFF
AI301 HI WARN 2
OFF, –99999.000 to +99999.000
AI301HW2 := OFF
AI301 HI ALARM
OFF, –99999.000 to +99999.000
AI301HAL := OFF
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...