4.54
SEL-787 Relay
Instruction Manual
Date Code 20081022
Protection and Logic Functions
Voltage-Based Protection
Volts/hertz tripping elements are usually used to trip the transformer breaker.
Volts/hertz logic is discussed in the following section.
and
are similar to
IEEE C37.102 : 2006 IEEE Guide
for
AC Generator Protection Figure 4.5.4-1
and
Figure 4.5.4-2
.
Figure 4.32
Dual-Level Volts/Hertz Time-Delay Characteristic 24CCS = DD
Figure 4.33
Composite Inverse/Definite-Time Overexcitation Characteristic, 24CCS = ID
.01
0.1
1.0
10
100
1000
100
110
120
130
140
24D2P2 = 118%
24D2D2 = 6 s
24D2P1 =
110%
Time (Minutes)
Transformer Limit Curve
on Gen. Voltage Base
Mfg-Generator
Limit Curve
Volts/Hertz (%)
Relay Characteristic
Time (Minutes)
Generator Manufacturer's
Recommended Protection Curve
Transformer Limit Curve on
Generator Voltage Base
.001
.01
0.1
1.0
10
100
100
110
120
130
140
Volts/Hertz (%)
1000
24D2P2 = 118%
24D2D2 = 1.2 s
24IP=108%
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...