4.6
SEL-734 Meter
Instruction Manual
Date Code 20090730
Metering
Demand Metering
Comparison of
Thermal, Rolling, and
Block Demand Meters
The example in
shows the response of thermal, rolling, and block
demand meters to a 1.0 per unit step energy input.
Figure 4.3
Response of Thermal, Rolling, and Block Demand Meters to a
Step Input (Setting DMTC=15 Minutes)
0
5
10
15
Time
(Minutes)
1.0
0.5
0
Instantaneous Current (per unit)
Step
Current
Input
0
5
10
15
Time
(Minutes)
1.0
0.9
0.5
0
Thermal Demand Current (per unit)
Thermal
Demand
Meter
Response
(EDEM=THM)
DMTC=15 minutes
0
5
10
15
Time
(Minutes)
1.0
0
0.67
0.33
Rolling Demand Current (per unit)
Rolling
Demand
Meter
Response
(EDEM=ROL)
DMTC=15 minutes
0
5
10
15
Time
(Minutes)
1.0
0
Block
Demand
Meter
Response
(EDEM=BLOK)
Summary of Contents for SEL-734
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 18: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 44: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 98: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 146: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 170: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 206: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 230: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 344: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...