Logic
Counter Variables
illustrates how to use the SEL
OGIC
control equation counters to
limit the demand by starting an on-site diesel generator.
EXAMPLE 8.2
Using Counters to Control Generator Starting via
Load Monitoring
When the three-phase demand is greater than 100 kW for greater
than 10 minutes, the diesel generator should start to pick up demand.
The generator should be started in 5 minutes when demand is > 125
kW. Also, if the demand is greater than 150 kW, the diesel generator
should start immediately. In order to achieve this function, make the
following settings:
ESC :=
1
ESV :=
10
SC01PV :=
60
SC01R :=
IN401
# disable the starting of the generator if desired
SC01LD :=
IN402 OR (MW3DI > 150)
# start the generator
immediately
SV10 :=
NOT(SV10T)
# 10 second period
SC01CU :=
R_TRIG SV10 AND (MW3DI > 100) OR
F_TRIG SV10 AND (MW3DI > 125)
# increment counter SC01,
faster when the demand is higher than 125.00
SC01CD :=
R_TRIG SV10 AND (MW3DI < 100)
# decrement counter
SC01 when the demand is below 100.00
OUT402 :=
(SC01 > 48)
# warning that diesel generator is about to
start
OUT401 :=
SC01QU
# start generator signal
Figure 8.12
SEL
OGIC
Variable SV10 Timing Logic
Because demands are slow changing values, it does not make sense to check
them continuously. The ten-second period on SV10T makes the preset value
setting easier to determine.
is provided as a reference to this example.
SC
n
QU
Output, Word Bit
This word bit output asserts when SC
n
= SC
n
PV.
SC
n
QD
Output, Word Bit
This word bit asserts when SC
n
= 0.
SC
n
Output, Analog
Value
Present counter value. Use with any analog compari-
son in SEL
OGIC
and view using the
COU
command.
Table 8.3
Counter Inputs and Outputs
(Sheet 2 of 2)
Name
Type
Description
NOTE
: SCn is stored in volatile
memory and is lost when the meter
loses power.
SV10
SV10T
5.00
5.00
Preset Value
10 minutes
60 s/minute
•
10 x/count
-------------------------------------------------------------
60 s/count
=
=
Summary of Contents for SEL-734
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 18: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 44: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 98: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 146: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 170: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 206: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 230: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 344: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...