Date Code 20010719
701 Motor Protection Relay
Modbus
®
RTU Communications Protocol
03h Read Holding Registers Command
C.7
03h Read Holding Registers Command
Use function code 03h to read directly from the Modbus Register map shown in
. You may read a maximum of 125 registers at once with this
function code. Most masters use 4X references with this function code. If you are
accustomed to 4X references with this function code, for 5-digit addressing, add 40001
to the standard database address.
Table C.6
03h Read Holding Registers Command
Table C.6
03h Read Holding Registers Command
Bytes
Field
The Master Request Must Have the Following Format
1 byte
Slave address
1 byte
Function code (03h)
2 bytes
Starting register address
2 bytes
Number of registers to read
2 bytes
CRC-16 for message
A Successful SEL-701 Relay Response Will Have the Following Format
1 byte
Slave address
1 byte
Function code (03h)
1 byte
Byte count (should be twice number of registers read)
n bytes
Byte count bytes of data
2 bytes
CRC-16 for message
Summary of Contents for SEL-701
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 36: ...This page intentionally left blank ...
Page 64: ...This page intentionally left blank ...
Page 144: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 232: ...This page intentionally left blank ...
Page 246: ...This page intentionally left blank ...
Page 346: ...This page intentionally left blank ...
Page 390: ...This page intentionally left blank ...
Page 408: ...This page intentionally left blank ...
Page 410: ......
Page 412: ......
Page 414: ......
Page 416: ......
Page 418: ......
Page 420: ......
Page 422: ......
Page 424: ......
Page 426: ......
Page 428: ......
Page 430: ......
Page 432: ......
Page 434: ......
Page 436: ......
Page 438: ......
Page 440: ......
Page 442: ......
Page 452: ...This page intentionally left blank ...