701 Motor Protection Relay
Settings Calculation
Output Configuration
4.45
Output Contact Fail-Safe, Trip Duration, & Starting Lockout Settings
Table 4.36
Output Contact Fail-Safe, Trip Duration, and Starting Lockout Settings
The SEL-701 Relay allows you to enable fail-safe output contact operation for
relay contacts on an individual basis. When contact fail-safe is enabled, the relay
output contact is held in its energized position when relay control power is applied and
falls to its deenergized position when control power is removed. Output contact
deenergized positions are indicated on the relay chassis and in
page 2.14 in Section 2: Installation
When TRIP Contact Failsafe is enabled and the TRIP output contact is
appropriately connected to the motor breaker or contactor, the motor is automatically
tripped when relay control power fails. This setting/connection philosophy is
appropriate if the protected motor is more valuable than the process that the motor
supports. In critical applications where the protected motor is not more valuable than
the process, you may want the motor to run even if the relay is out of service. In this
case, disable TRIP Contact Failsafe by selecting N.
The Minimum Trip Duration Time is the minimum amount of time that the relay
trip signal will last in the event of a fault. Set this time at least as long as your motor
breaker operate time or your motor contactor dropout time. In the event of a thermal
element trip or a trip caused by the starts per hour limit or minimum time between
starts function, the trip signal will remain until the motor thermal estimate has cooled
or time has passed to permit another start.
Antibackspin Setting
Table 4.37
Antibackspin Setting
In certain pump applications, fluid flowing backward through the pump may spin
the pump motor for a short time after the motor is stopped. It is dangerous to attempt to
Table 4.36
Output Contact Fail-Safe and Trip Duration Settings
Setting Prompt
Setting Range
Setting Name =
Factory Default
Enable TRIP Contact Failsafe
Y, N
TRFS = Y
Enable OUT1 Contact Failsafe
Y, N
OUT1FS = N
Enable OUT2 Contact Failsafe
Y, N
OUT2FS = N
Enable OUT3 Contact Failsafe
Y, N
OUT3FS = N
Minimum Trip Duration Time
0.00–400.00 s
TDURD = 0.50
Table 4.37
Antibackspin Setting
Setting Prompt
Setting Range
Setting Name = Factory Default
Antibackspin Starting Delay
0–60 min
ABSDLY = 0
Summary of Contents for SEL-701
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 36: ...This page intentionally left blank ...
Page 64: ...This page intentionally left blank ...
Page 144: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 232: ...This page intentionally left blank ...
Page 246: ...This page intentionally left blank ...
Page 346: ...This page intentionally left blank ...
Page 390: ...This page intentionally left blank ...
Page 408: ...This page intentionally left blank ...
Page 410: ......
Page 412: ......
Page 414: ......
Page 416: ......
Page 418: ......
Page 420: ......
Page 422: ......
Page 424: ......
Page 426: ......
Page 428: ......
Page 430: ......
Page 432: ......
Page 434: ......
Page 436: ......
Page 438: ......
Page 440: ......
Page 442: ......
Page 452: ...This page intentionally left blank ...