Controlling Output Contacts and Remote Bits Using Modbus
C.14
Controlling Output Contacts
and Remote Bits Using Modbus
The SEL-701-1 Monitor Modbus Register Map (
includes three fields that allow a Modbus Master to control monitor output contacts and
Relay Word Remote Bits (see
Appendix B: SELogic® Control Equations and
). Use Modbus function codes 06h or 10h to write the appropriate
command codes and parameters into the registers shown in
defines the command codes, their function and associated parameters,
and the function code used to initiate the code.
Table C.14
SEL-701-1 Monitor Modbus Command Region
Address
Field
0030h
Command Code
0031h
Parameter 1
0032h
Parameter 2
Table C.15
Modbus Command Codes
Command
Code
Function
Parameter Definition
Modbus
Function
Code
01
a
Start
No Parameters
06h, 10h
02
a
Stop
No Parameters
06h, 10h
03
a
Emergency
Restart
No Parameters
06h, 10h
04
a
Reset Trip,
Targets
No Parameters
06h, 10h
05
Pulse Output
Contacts
Parameter 1:
1
TRIP
2
OUT1
3
OUT2
4
OUT3
5
ALARM
Parameter 2:
1-15; Pulse duration in minutes
Default to 1 second if not supplied10h
Default to 1 second if not supplied10h
10h
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...