Date Code 20011009
SEL-701-1 Monitor
Modbus
®
RTU Communications Protocol
07h Read Exception Status Command
C.11
07h Read Exception Status Command
The SEL-701-1 Monitor uses this function to allow a Modbus master to read the
present status of the monitor and protected motor.
If the bit is set (1), the output contact is asserted or the motor is in the indicated
condition. If the bit is cleared (0), the output contact is deasserted or the motor is not in
the indicated condition. In the event that both Bits 6 and 7 are cleared, the motor is
starting.
Table C.11
07h Read Exception Status Command
Bytes
Field
The Master Request Must Have the Following Format
1 byte
Slave address
1 byte
Function code (07h)
0 bytes
No data fields are sent
2 bytes
CRC-16 for message
A Successful SEL-701-1 Monitor Response Will Have the Following Format
1 byte
Slave address
1 byte
Function code (07h)
1 byte
Status byte
2 bytes
CRC-16 for message
The Status Byte is Sent LSB-First, and Consists of the Following Bits
Bit 0
Trip Output Status
Bit 1
OUT1 Output Status
Bit 2
OUT2 Output Status
Bit 3
OUT3 Output Status
Bit 4
ALARM Output Status
Bit 5
0
Bit 6
Motor Stopped
Bit 7
Motor Running
Summary of Contents for SEL-701-1
Page 16: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 34: ...This page intentionally left blank ...
Page 118: ...This page intentionally left blank ...
Page 142: ...This page intentionally left blank ...
Page 196: ...This page intentionally left blank ...
Page 210: ...This page intentionally left blank ...
Page 242: ...This page intentionally left blank ...
Page 384: ...This page intentionally left blank ...