3.5
Date Code 20020903
SEL-587Z Instruction Manual
Relay Elements
High-Impedance Protection
Figure 3.6
CT Characteristic.
This is a very pessimistic value, because the current transformer completely
saturates only under extreme conditions. Comparing the calculated value with
the CT knee-point voltage,
shows that 178 V is well below the
knee-point voltage of 432 V.
Set the voltage elements of the high-impedance relay for the maximum
possible voltage developed across the elements for an external fault as
follows:
Equation 3.3
where
V
s
= voltage setting
K
= a safety factor, representing the necessary security
level and CT performance
For this example, choose K as 150 percent. Follow your company practices for
setting this safety factor in your particular application.
Equation 3.4
Set the high-impedance elements 87A1P = 87B1P = 87C1P = 267 V.
Minimum
Internal Fault
Operating Current
Use the following equation to calculate the minimum primary current required
to operate the relay for an internal fault:
Equation 3.5
0.01
0.10
1.00
10.00
100.00
10
100
1000
Se
co
nda
ry
R
M
S
Ex
citing
Vo
lts
Secondary RMS Exciting Amperes
V
s
K
V
r
•
=
V
s
1.5
V
r
•
=
1.5
178
•
=
267 V
=
I
min
n
I
e
I
r
I
m
+
+
•
(
)
N
•
=
Summary of Contents for SEL-587Z
Page 10: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 66: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...