B.6
SEL-587Z Instruction Manual
Date Code 20020903
Firmware Upgrade Instructions
Save Settings and Other Data
Figure B.7
Correcting Communications Parameters.
Step 5. From the Call menu, choose Connect to reestablish
communication with the relay.
Step 6. Press
<Enter>
to obtain the “=” prompt in the terminal
emulation window.
C Save Settings and Other Data
If the relay contains History (HIS), Event (EVE), Metering (MET), or
Sequential Events Recorder (SER) data that you want to retain, retrieve and
record this information prior to performing the firmware upgrade.
Enter Access Level 2
Step 1. Using the communications terminal, at Access Level 0 type
ACC<Enter>
.
Step 2. Type the Access Level 1 password and press
<Enter>
.
You will see the => action prompt.
Step 3. Type
2AC<Enter>.
Step 4. Type the correct Access Level 2 password.
You will see the =>> action prompt.
View Passwords and FID
Step 1. Type
PAS<Enter>
at Access Level 2 to view relay passwords.
Make a written record of the original password settings in case
you need these passwords later.
Step 2. Type
ID<Enter>
to view the relay firmware identifier (FID).
Make a written record of the FID identifier number for use in
Download Existing Firmware on page B.9
of this document.
Backup Relay Settings
The relay preserves the settings and passwords during the firmware upgrade
process. However, if relay power is interrupted during the firmware upgrade
process, the relay can lose the settings. Make a copy of the original relay
Summary of Contents for SEL-587Z
Page 10: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 66: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...