Schweitzer Engineering Laboratories, Inc.
SEL-487V Data Sheet
27
Radiated RF Immunity:
IEEE C37.90.2-2004
IEC 61000-4-3:2006 + A1:2007 +
A2:2010
20 V/m (>35 V/m, 80% AM, 1 kHz)
Sweep: 80 MHz to 1 GHz
Spot: 80, 160, 450, 900 MHz
10 V/m (>15 V/m, 80% AM, 1 kHz)
Sweep: 80 MHz to 1 GHz
Sweep: 1.4 GHz to 2.7 GHz
Spot: 80, 160, 380, 450, 900, 1850,
2150 MHz
Electrical Fast Transient
Burst (EFTB):
IEC 61000-4-4:2012
Zone A:
±2 kV: Communication ports
±4 kV: All other ports
Surge Immunity:
IEC 61000-4-5:2005
Zone A:
±2 kV
L-L
±4 kV
L-E
±4 kV: communication ports
(Ethernet)
Note:
Cables connected to EIA-422,
G.703, EIA-232, and IRIG-B
communications ports shall be less than
10 m in length for Zone A compliance.
Zone B:
±1 kV
L-L
: 24–48 Vdc power supply
±2 kV
L-E
: 24–48 Vdc power supply
±2 kV: communication ports (except
Ethernet)
Note:
Cables connected to EIA-232
communications ports shall be less
than 10 m in length for Zone B
compliance.
Conducted Immunity:
IEC 61000-4-6:2013
20 V/m; (>35 V/m, 80% AM, 1 kHz)
Sweep: 150 kHz–80 MHz
Spot: 27, 68 MHz
Power Frequency Immunity
(DC Inputs):
IEC 61000-4-16:2015
Zone A:
Differential: 150 V
RMS
Common Mode: 300 V
RMS
Power Frequency Magnetic
Field:
IEC 61000-4-8:2009
Level 5:
100 A/m;
60 Seconds; 50/60 Hz
1000 A/m 1 to 3 Seconds; 50/60 Hz
Note:
50G1P
0.05 (ESS = N, 1, 2)
50G1P
0.1 (ESS = 3, 4)
Power Supply Immunity:
IEC 61000-4-11:2004
IEC 61000-4-17:1999/A1:2001/A2:2008
IEC 61000-4-29:2000
AC Dips & Interruptions
Ripple on DC Power Input
DC Dips & Interruptions
Gradual Shutdown/Startup (DC only)
Discharge of Capacitors
Slow Ramp Down/Up
Reverse Polarity (DC only)
Damped Oscillatory
Magnetic Field:
IEC 61000-4-10:2016
Level 5:
100 A/m
EMC Compatibility
Product Standards:
IEC 60255-26:2013
Emissions:
IEC 60255-26:2013, Section 7.1
Class A
47 CFR Part 15B
Class A
Canada ICES-001 (A) / NMB-001 (A)
Environmental
Product Standards:
IEC 60255-27:2013
Cold, Operational:
IEC 60068-2-1:2007
Test Ad: 16 hours at –40°C
Cold, Storage:
IEC 60068-2-1:2007
Test Ad: 16 hours at –40°C
Dry Heat, Operational:
IEC 60068-2-2:2007
Test Bd: 16 hours at +85°C
Dry Heat, Storage:
IEC 60068-2-2:2007
Test Bd: 16 hours at +85°C
Damp Heat, Cyclic:
IEC 60068-2-30:2005
Test Db: +25 °C to +55°C, 6 cycles (12 +
12-hour cycle), 95% RH
Damp Heat, Steady State:
IEC 60068-2-78:2013
Severity: 93% RH, +40°C, 10 days
Cyclic Temperature:
IEC 60068-2-14:2009
Test Nb: –40°C to +80°C, 5 cycles
Vibration Resistance:
IEC 60255-21-1:1988
Class 2 Endurance, Class 2 Response
Shock Resistance:
IEC 60255-21-2:1988
Class 1 Shock Withstand, Class 1 Bump
Withstand, Class 2 Shock Response
Seismic:
IEC 60255-21-3:1993
Class 2 Quake Response
Event Reports
High-Resolution Data
Rate:
8000 samples/second
4000 samples/second
2000 samples/second
1000 samples/second
Output Format:
Binary COMTRADE
Note:
Per IEEE Standard Common Format for Transient
Data Exchange (COMTRADE) for Power Systems, IEEE C37.111-
1999.
Event Reports
Length:
15/30 cycles
Maximum Duration:
Five records of 24 seconds each at
1000 samples/second
Resolution:
1/4 and 1/8 samples/cycle
Digital Inputs:
2 kHz
Event Summary
Storage:
100 summaries
Breaker History
Storage:
128 histories
Sequential Events Recorder
Storage:
1000 entries
Trigger Elements:
250 relay elements
Processing Specifications
AC Voltage and Current Inputs
8000 samples per second, 3 dB low-pass analog filter cut-off
frequency at 646 Hz, ± 5%
Digital Filtering
Two-Cycle and Full-cycle cosine after low-pass analog filtering
Protection and Control Processing
4, 8, and 32 times per power system cycle
Control Points
32 remote bits
32 local control bits
32 latch bits in protection logic
32 latch bits in automation logic