8.27
Date Code 20171021
Instruction Manual
SEL-421 Relay
Settings
Group Settings
Make
settings if Group setting ECOMM := POTT, POTT2, POTT3,
DCUB1, or DCUB2. Some settings are not required for every mode (see
for details).
NOTE:
If the relay is using a remote
data acquisition system, such as TiDL,
the operating times will be delayed by
1.5 ms. Use caution when setting the
relay coordination times to account
for this added delay.
Make
settings if Group setting ECOMM := DCUB1 or DCUB2.
NOTE:
If the relay is using a remote
data acquisition system, such as TiDL,
the operating times will be delayed by
1.5 ms. Use caution when setting the
relay coordination times to account
for this added delay.
Table 8.67
POTT Trip Scheme
Setting
Prompt
Default
Value
Increment
Z3RBD
Zone 3 Reverse Block Time Delay
(0.000–16000 cycles)
5.000
0.125
EBLKD
Echo Block Time Delay (OFF, 0.000–16000 cycles)
10.000
0.125
ETDPU
Echo Time Delay Pickup (OFF, 0.000–16000 cycles)
2.000
0.125
EDURD
Echo Duration Time Delay (0.000–16000 cycles)
4.000
0.125
EWFC
Weak Infeed Trip (Y, N, SP)
N
27PWI
Weak Infeed Phase Undervoltage Pickup
(1.0–200 V secondary)
47
0.1
27PPW
Weak Infeed Phase-to-Phase Undervoltage Pickup
(1.0–300 V secondary)
80
0.1
59NW
Weak Infeed Zero-Sequence Overvoltage Pickup
(1.0–200 V secondary)
5
0.1
PT1
General Permissive Trip Received
(SEL
OGIC
Equation)
IN102
AND
PLT02
PT3
Three-Pole Permissive Trip Received
(SEL
OGIC
Equation)
NA
PTA
A-Phase Permissive Trip Received
(SEL
OGIC
Equation)
NA
PTB
B-Phase Permissive Trip Received
(SEL
OGIC
Equation)
NA
PTC
C-Phase Permissive Trip Received
(SEL
OGIC
Equation)
NA
EPTDIR
Enable Directional Element Permissive Trip (Y, N)
N
PTDIR
Dir. Ele. Permissive Trip Recvd (SEL
OGIC
Equation)
NA
COMZDTC Dir. Ele. Comm.-Assisted Trip Enable (SEL
OGIC
Equation)
NA
Table 8.68
DCUB Trip Scheme
Setting
Prompt
Default
Value
Increment
GARD1D Guard Present Security Delay (0.000–16000 cycles)
120.000
0.125
UBDURD DCUB Disabling Time Delay (0.000–16000 cycles)
180.000
0.125
UBEND
DCUB Duration Time Delay (0.000–16000 cycles)
20.000
0.125
PT2
Channel 2 Permissive Trip Received (SEL
OGIC
Equation) NA
LOG1
Channel 1 Loss-of-Guard (SEL
OGIC
Equation)
NA
LOG2
Channel 2 Loss-of-Guard (SEL
OGIC
Equation)
NA
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...