![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 500](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726500.webp)
6.164
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
Circuit Breaker Failure Application Examples
To maintain system stability, you must clear the fault within the total clearing
time. Use the maximum operating time of the local and remote circuit breakers.
The maximum operating time of the circuit breaker, t
l-bk
, is 2 cycles for this
example. Also use the maximum reset time of 50FA1; the maximum reset (drop-
out) time of the phase current level detector, t
50r
, is 1 cycle. You must also
include the communications channel time, t
ch
, for remote circuit breaker tripping.
To determine setting BFPU1, you must find the safety margin, t
s
. Determine the
Equation 6.93
Use the safety margin result from
to calculate BFPU1:
Equation 6.94
BFPU1 :=
10.000
.
Breaker Failure Time Delay—BK1 (0.000–6000 cycles)
Figure 6.47
Timing Diagram for Setting BFPU1—Scheme 2
Breaker
Operate Time t
l-bk
BFPU1
SPBFPU1
Line Protection
Maximum Operate Time
Fault Occurs
50FA1
BFIA1
FBF1
50FA1
Dropout Time, t
50r
Safety
Margin Time, t
s
where:
t
s
= safety margin
t
t
= total clearing time (15 cycles)
t
lr
= line protection maximum operating time (2 cycles)
t
l-bk
= local circuit breaker maximum operating time (2 cycles)
t
50r
= circuit breaker failure overcurrent element 50FA1 maximum
reset time (1 cycle)
t
86
= auxiliary breaker failure relay operating time (1 cycle)
t
ch
= communications channel maximum operating time (1 cycle)
t
r-bk
= remote circuit breaker maximum operating time (2 cycles)
t
s
t
t
t
1r
t
1 bk
–
t
50r
t
86
t
ch
t
r bk
–
+
+
+
+
+
–
=
15
2 2 1 1 1 2
+
+
+
+
+
–
=
6 cycles
=
BFPU1
t
1 bk
–
t
50r
t
s
+
+
=
3 1 6
+
+
=
10 cycles
=
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...