6.160
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
Circuit Breaker Failure Application Examples
BFTRIP1 (Breaker Failure Trip for Circuit Breaker BK1). Assign a control input
that is energized externally to signal the relay when the circuit breaker failure trip
clears the fault successfully.
BFULTR1 :=
IN104
.
Breaker Failure Unlatch Trip—BK1 (SEL
OGIC
Equation)
Control Outputs
Use SEL
OGIC
control equations to assign control outputs for tripping Circuit
Breaker BK1, retripping Circuit Breaker BK1, and circuit breaker failure trip-
ping.
shows dc connections for the circuit breaker failure trip and cir-
cuit breaker trip/retrip.
Use the main board high current interrupting control output for the retrip signal
(RT1) because this output can interrupt large circuit breaker coil currents. There
is no TDUR3D (3PT Minimum Trip Duration Time Delay) for RT1; the RT1 sig-
nal can drop out while there is current flowing through the trip coil, if the auxil-
iary circuit breaker contacts have not yet opened.
OUT101 :=
3PT
.
OUT103 :=
RT1
.
OUT107 :=
BFTRIP1
.
Example Completed
This completes the application example that describes setting of the SEL-421 for
circuit breaker failure protection. Analyze your particular power system to deter-
mine the appropriate settings for your application.
Relay Settings
lists all protective relay settings applied for this example.
Figure 6.44
Circuit Breaker Failure Trip and Circuit Breaker Trip DC
Connections
86-1
86-1
86-1
BFTRIP1
(OUT107)
DC1 (—)
DC2 (—)
DC2 (+)
DC1 (+)
TC-1
3PT
(OUT101)
TRIP COIL #2
TRIP COIL #1
CBF LOCKOUT
TC-2
52AA1
RT1
(OUT103)
DC3 (—)
DC3 (+)
52AA1
Table 6.42
Settings for Circuit Breaker Failure Example 1 (Sheet 1 of 2)
Setting
Prompt
Entry
Relay Configuration (Group)
EBFL1
Breaker 1 Failure Logic (N, 1, 2, Y1, Y2)
1
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...