6.136
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
Out-of-Step Logic Application Examples
Example Completed
This completes the application example that describes setting the SEL-421 for
out-of-step tripping. Analyze your particular power system to determine the
appropriate settings for your application.
Relay Settings
lists the settings that the relay automatically calculates and hides when
you set EADVS to N.
list the protective relay settings available in this example.
Table 6.36
Automatically Calculated/Hidden Settings
Setting
Prompt
Default Setting
X1B7
Zone 7 Reactance—Bottom (–0.05 to –140
secondary) X1B7 = –X1T7
X1B6
Zone 6 Reactance—Bottom (–0.05 to –140
secondary) X1B6 = –X1T6
R1L7
Zone 7 Resistance—Left (–0.05 to –140
secondary)
R1L7 = –R1R7
R1L6
Zone 6 Resistance—Left (–0.05 to –140
secondary)
R1L6 = –R1R6
50ABCP
Positive-Sequence Current Supervision
(1.00–100 A secondary)
50ABCP = 0.2 • I
NOM
50QUBP
Negative-Sequence Current Supervision
(OFF, 0.50–100 A secondary)
OFF
UBD
Negative-Sequence Current Unblock Delay
(0.500–120 cycles)
0.500
UBOSBF
Out-of-Step Angle Unblock Rate (1–10)
4
Table 6.37
Relay Configuration (Group)
Setting
Prompt
Entry
EOOS
Out-of-Step
Y
EADVS
Advanced Settings (Y, N)
N
Table 6.38
Out-of-Step Tripping/Blocking (Sheet 1 of 2)
Setting
Prompt
Entry
OOSB1
Block Zone 1 (Y, N)
Y
OOSB2
Block Zone 2 (Y, N)
Y
OOSB3
Block Zone 3 (Y, N)
N
OSBD
Out-of-Step Block Time Delay (0.500–8000 cycles)
1.500
OSBLTCH Latch Out-of-Step Blocking (Y, N)
Y
EOOST
Out-of-Step Tripping (N, I, O)
O
OSTD
Out-of-Step Trip Delay (0.500–8000 cycles)
0.875
X1T7
Zone 7 Reactance—Top (0.05 to 140
secondary)
96.00
X1T6
Zone 6 Reactance—Top (0.05 to 140
secondary)
95.00
R1R7
Zone 7 Resistance—Right (0.05 to 140
secondary)
15.53
R1R6
Zone 6 Resistance—Right (0.05 to 140
secondary)
5.87
X1B7
Zone 7 Reactance—Bottom (–0.05 to –140
secondary)
–96.00
X1B6
Zone 6 Reactance—Bottom (–0.05 to –140
secondary)
–95.00
R1L7
Zone 7 Resistance—Left (–0.05 to –140
secondary)
–15.53
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...