6.121
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
Out-of-Step Logic Application Examples
The OSB logic typically supervises forward-looking Zone 1 and Zone 2 because
the operation time of these two zones is ordinarily shorter than the time period
during which the impedance of a power swing resides in these protection zones.
For example, if the period of a swing is 1.5 seconds, OSB logic should supervise
instantaneous Zone 1 and communications-assisted Zone 2.
During a power swing, the relay typically does not block overreaching zones of
protection that provide time-delayed tripping. Do not block reverse-looking
Zone 3 when this zone serves as a starting element for the DCB (directional com-
parison blocking) scheme or when this zone provides current reversal guard for
the POTT (permissive overreaching transfer tripping) scheme. For example, if the
OSB logic inhibits the DCB blocking signal during swings that pass behind the
local relay, over-tripping can occur at the remote terminal. If a power swing
enters both the local reverse-looking Zone 3 and the remote overreaching Zone 2,
high-speed tripping occurs at the remote terminal because OSB logic removes the
local Zone 3 element DCB scheme block.
Set the relay to block Zone 1 and Zone 2.
OOSB1 :=
Y
.
Block Zone 1 (Y, N)
OOSB2 :=
Y
.
Block Zone 2 (Y, N)
OOSB3 :=
N
.
Block Zone 3 (Y, N)
Zone 6 and Zone 7 Impedance Settings
The OOS logic uses two zones of concentric polygons, outer Zone 7 and inner
Zone 6 (see
). The relay uses Zone 6 and Zone 7 for OOS logic timing
to differentiate between power swings and faults. The relay measures a traveling
Figure 6.29
OOS Characteristic Settings Parameters
S
R
Zone 2
Zone 1
Minimum
Load
Impedance
(Export)
R1
X1
X1T7
X1B7
X1T6
X1B6
R1R6
R1L6
R1R7
Z1 Trajectory
R1L7
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...