Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Quadrilateral Ground Polarizing Quantity
Advanced Settings are enabled, so you must enter two final settings for the quad-
rilateral ground-distance protection. With setting XGPOL, you can choose the
polarizing quantity for the quadrilateral ground-distance protection. You can
choose either negative-sequence current (I2) or zero-sequence current (IG).
Choose the appropriate quantity to reduce overreach and underreach of the reac-
tance line. The reactance line can underreach or overreach during high-resistance
single phase-to-ground faults because of nonhomogeneous negative-sequence or
zero-sequence networks, and prefault load flow.
shows the network to determine negative-sequence or zero-sequence
homogeneity.
Z
left
is the total impedance up to the fault (F) on the left side of the fault location,
while Z
right
is the total impedance up to the fault on the right side of the network.
A network is homogeneous with respect to the particular fault location if
is satisfied:
Equation 6.58
Use
to determine the zero-sequence and nega-
tive-sequence homogeneity:
Equation 6.59
Equation 6.60
The values T
0
and T
2
represent how much the apparent fault impedance mea-
sured by XAG tilts up or down (electrical degrees) because of the nonhomogene-
ity of the corresponding network.
illustrates the possible tilt
situations caused by a nonhomogeneous network.
Figure 6.22
Circuit to Determine Network Homogeneity
Zleft
Zright
S
IF
IF
IFS
IFR
ZS
ZR
m ZL
(1—m) ZL
R
F
X
left
R
left
------------
X
right
R
right
---------------
=
T
0
ARG
Z
0S
Z
0L
Z
0R
+
+
1 m
–
Z
0L
Z
0R
+
•
---------------------------------------------------
=
T
2
ARG
Z
1S
Z
1L
Z
1R
+
+
1 m
–
Z
1L
Z
1R
+
•
---------------------------------------------------
=
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...