Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Convert the power system impedances from primary to secondary so you can
later calculate protection settings.
lists the corresponding secondary
quantities. Convert the impedances to secondary ohms as follows:
Equation 6.52
Equation 6.53
The maximum load current of 777 A primary occurs when the parallel cable is
out of service.
Cable Admittances:
Y
1L1
= Y
1L2
Y
0L1
= Y
0L2
j6.71 • 10
–6
S primary (susceptance)
j6.71 • 10
–6
S primary (susceptance)
Source S Impedances:
Z
1S
= Z
0S
50
87° primary
Source R Impedances:
Z
1R
= Z
0R
35
87° primary
PTR (potential transformer ratio)
230 kV:115 V = 2000
CTR (current transformer ratio)
1000:5 = 200
Phase Rotation
ABC
Table 6.23
Secondary Impedances
Parameter
Value
Cable Impedances:
Z
1L1
= Z
1L2
Z
0L1 (sheath return only)
= Z
0L2 (sheath return only)
Z
0L1 (ground return only)
= Z
0L2 (ground return only)
Z
0L1 (sheath and ground return)
= Z
0L2 (sheath and ground return)
0.48
42.5° secondary
0.95
17.4° secondary
9.14
84.9° secondary
0.96
21.7° secondary
Cable Admittance:
Y
1L1
= Y
1L2
Y
0L1
= Y
0L2
6.71 • 10
–5
S
90° secondary
6.71 • 10
–5
S
90° secondary
Source S Impedances:
Z
1S
= Z
0S
5.0
87° secondary
Source R Impedances:
Z
1R
= Z
0R
3.5
87° secondary
Table 6.22
System Data—230 kV Parallel Underground Cables (Sheet 2 of 2)
Parameter
Value
k
CTR
PTR
------------
200
2000
------------
0.1
=
=
=
Z
1L1 secondary
k Z
1L1 primary
•
=
0.10 4.78
42.5
•
=
0.48
42.5
=
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...