6.57
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
Current and Voltage Source Selection
The voltage and current source selection is for one circuit breaker. The relay
derives the line current source from current input IW when you set ESS to N.
ESS :=
N
.
Current and Voltage Source Selection (Y, N, 1, 2, 3, 4)
illustrates the current and voltage sources for this particular applica-
tion. The relay uses potential input VY and current input IW for line relaying;
potential input VAZ is for synchronism check.
Synchronism Check on page 5.158
describes how to apply the synchronism check function.
Breaker Monitor
Circuit Breaker Configuration
Set the relay to indicate that Circuit Breaker 1 is a three-pole trip circuit breaker.
BK1TYP :=
3
.
Breaker 1 Trip Type (Single-Pole = 1, Three-Pole = 3)
Circuit Breaker 1 Inputs
The SEL-421 uses a normally open auxiliary contact from the circuit breaker to
determine whether the circuit breaker is open or closed.
52AA1 :=
IN101
.
A-Phase N/O Contact Input -BK1 (SEL
OGIC
Equation)
Group Settings
Line Configuration
The SEL-421 has four transformer turns ratio settings that convert the secondary
potentials and currents that the relay measures to the corresponding primary val-
ues. These settings are the potential transformer and current transformer ratios
PTRY, PTRZ, CTRW, and CTRX. Use the Y potential input for line relaying and
the Z potential input for synchronism checks. Use the W current input for line
relaying. The settings VNOMY and VNOMZ specify the nominal secondary
line-to-line voltage of the potential transformers (see
CTRW :=
200
.
Current Transformer Ratio—Input W (1–50000)
PTRY :=
3000
.
Potential Transformer Ratio—Input Y (1–10000)
VNOMY :=
115
.
PT Nominal Voltage (L–L)—Input Y (60–300 V secondary)
PTRZ :=
3000
.
Potential Transformer Ratio—Input Z (1–10000)
VNOMZ :=
115
.
PT Nominal Voltage (L–L)—Input Z (60–300 V secondary)
Figure 6.12
Circuit Breaker Arrangement at Station S
SEL-421
VAZ
IW
VY
BK1
3
1
3
34
5 kV Bus
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...