6.12
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
230 kV Overhead Distribution Line Example
for the ground-distance elements and residual ground directional overcurrent ele-
ments. A polarizing quantity was not available for choice I, so I is not selected for
this particular application example.
ORDER :=
QV
.
Ground Directional Element Priority (combine Q, V, I)
SEL
OGIC
control equation E32IV must assert to logical 1 to enable V or I for
directional control of the ground-distance elements and residual ground direc-
tional overcurrent elements. Set E32IV equal to logical 1.
E32IV :=
1
.
Zero-Sequence Voltage and Current Enable (SEL
OGIC
Equation)
Pole-Open Detection
The setting EPO offers two options for deciding what conditions signify an open
pole, as listed in
.
Select the second option because a 52A contact is available. The relay uses both
open-phase detection and status information from the circuit breaker to make the
most secure decision.
EPO :=
52
.
Pole-Open Detection (52, V)
Pole-Open Time Delay on Dropout
The setting 3POD establishes the time delay on dropout after the Relay Word bit
3PO deasserts. This delay is important when you use line-side potential trans-
formers for relaying. Use the 3POD setting to stabilize the ground-distance ele-
ments in case of pole scatter during closing of the circuit breaker.
3POD :=
0.500
.
Three-Pole Open Time Dropout Delay (0.000–60 cycles)
Trip Logic
This logic configures the relay for tripping. These settings consist of four catego-
ries:
➤
Trip equations
➤
Trip unlatch options
➤
Trip timers
➤
Three-pole tripping enable
Table 6.4
Options for Enabling Pole-Open Logic
Option
Description
EPO := V
The logic declares a single-pole open if the corresponding phase undervoltage
element asserts and the open-phase detection logic declares the pole is open.
Select this option only if you use line-side potential transformers for relaying
purposes. A typical setting for the 27PO, pole-open undervoltage threshold, is
60 percent of the nominal line-to-neutral voltage.
Do not select this option when shunt reactors are applied because the voltage
slowly decays after the circuit breaker opens. With this option selected, the
relay can incorrectly declare LOP during a pole-open condition if there is
charging current that exceeds the pole-open current threshold.
EPO := 52
The logic declares a single-pole open if the corresponding 52A contact (e.g.,
52AA1) from the circuit breaker deasserts and the open-phase detection logic
declares that the pole is open.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...