5.175
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Functions
Synchronism Check
chronism-Check Voltage Source 2 (ASYNCS2) and corresponding settings
AKS2M and AKS2A for the regular Synchronism-Check Voltage Source 2 val-
ues SYNCS2, KS2M, and KS2A. The result is a normalized synchronism-check
voltage source V
S2
derived from the alternative source.
Example 5.1
shows an extra circuit breaker (BK3) and a generator position
added to the existing example system of
. You can monitor the
voltage at the generator position by connecting a single-phase voltage to
remaining voltage input VCZ (see
). Make setting
ASYNCS2 := VCZ to designate this relay voltage input as the alternate syn-
chronism-check voltage source.
ASYNCS2 :=
VCZ
.
Alternative Synchronism Source 2 (VAY, VBY, VCY,
VAZ, VBZ, VCZ)
For this new synchronism source voltage connection, adjust the source-to-
reference magnitude ratio with setting AKS2M and the source-to-reference
angle compensation with setting AKS2A, considering the settings for
age Magnitude and Angle Compensation on page 5.163
, the Bus 2 voltage is the regular Synchronism-
Check Voltage Source 2 for synchronism check across Circuit Breaker BK2.
However, if Circuit Breaker BK3 is open and the generator switch is closed,
the Synchronism-Check Voltage Source 2 transfers to the alternative Syn-
chronism-Check Voltage Source 2 the voltage from the generator position.
Figure 5.131
Alternative Synchronism-Check Source 2 Example and Settings
Bus 1
Line
Switch
SYNCS2 — designate voltage input
KS2M — adjust magnitude to reference
KS2A — adjust angle to reference
Bus 2
BK2
BK3
BK1
Generator
Synchronism-Check Voltage Source 2
ASYNCS2 — designate voltage input
AKS2M — adjust magnitude to reference
AKS2A — adjust angle to reference
ALTS2
— enable alternative source 2
Alternative Synchronism-Check Voltage Source 2
1
3
1
1
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...