SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Synchrophasors
SEL Fast Message Synchrophasor Protocol
See the SEL application guide “Using SEL-421 Relay Synchrophasors in Basic
Applications” (AG2002-08) for more information on the SEL Fast Message Syn-
chrophasor protocol.
Fast Message Synchrophasor Settings
The settings for SEL Fast Message synchrophasors are listed in
Many of these settings are identical to the settings for the C37.118 format (see
Settings for Synchrophasors on page 18.6
).
Certain settings in
are hidden, depending on the status of other set-
tings. For example, if PHDATAI := NA, the PHCURR setting is hidden to limit
the number of settings for your synchrophasor application.
The SEL Fast Message Synchrophasor Protocol always includes the frequency
information in floating-point representation, and fourteen user-programmable
SEL
OGIC
variables PSV49–PSV64. There are no user-programmable analog
quantities in the SEL Fast Message Synchrophasor Protocol.
Communications Bandwidth
A phasor measurement unit (PMU) that is configured to transmit a single syn-
chrophasor (positive-sequence voltage, for example) at a message period of one
second places little burden on the communications channel. As more synchro-
phasors are added, or if the message rate is increased, some communications
channel restrictions come into play.
Table 18.19
PMU Settings in the Relay for SEL Fast Message Protocol (in Global
Settings)
Setting
Description
EPMU
Enable Synchronized Phasor Measurement (Y, N)
MFRMT
Message Format (C37.118, FM)
a
a
C37.118 = IEEE Std C37.118. FM := SEL Fast Message. Set MFRMT := FM to enter the Fast Message
settings.
PMAPP
PMU Application (F = Fast Response, N = Narrow Bandwidth, 1 = Extra Narrow
b
)
b
Option 1 is not available when MFRMT = FM.
PMLEGCY
c
c
PMLEGCY must be set to Y to access the data configuration settings shown in this table.
Synchrophasor Legacy Settings (Y, N)
PHCOMP
Frequency-Based Phasor Compensation (Y, N)
PMID
PMU Hardware ID (0–4294967295)
PHVOLT
Include Voltage Terminal
PHDATAV
Phasor Data Set, Voltages (V1, ALL)
V
k
COMP
d
d
k = voltage terminal.
V
k
Voltage Angle Compensation Factor (–179.99 to +180 degrees)
PHCURR
e
e
Setting hidden when PHDATAI := NA.
Current Source
PHDATAI
f
f
When PHDATAV:= V1, this setting is forced to NA and cannot be changed.
Phasor Data Set, Currents (ALL, NA)
I
n
COMP
g
g
n = current terminal.
In Angle Compensation Factor (–179.99 to +180 degrees)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...