10.10
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Testing, Troubleshooting, and Maintenance
Test Methods
Testing With SER
You can set the relay to generate a report from the SER to test relay elements;
include the element that you want to test in the SER
Points and Aliases
list. Set
aliases for the element name, set state, and clear state in the relay SER to simplify
reading the SER report. See
Sequential Events Recorder (SER) on page 9.28
for
complete information on the SER.
Example: Testing the SEL-451 51S1 Element Using the SER
The SER gives exact time data for testing time-overcurrent element time-outs.
Subtract the 51S1T assertion time from the 51S1 assertion time to check the
operation time for this element. Use the factory defaults for the operating quan-
tity, pickup level, curve, time dial, electromechanical reset, and torque control
(
The procedure in the following steps shows how to set the SER trigger lists to
capture the selectable operating quantity time-overcurrent element 51S1 operat-
ing times. The procedure also shows how to set the torque control supervision for
the 51S1 element.
and
to determine the operating time
for the 51S1 element. For a current input 50 percent greater than the default
pickup, the test value, I
TEST
, is:
Equation 10.1
where M is the pickup multiple and 51S1P is the element pickup value (see
Table 10.4
Selectable Operating Quantity Time-Overcurrent Element (51S1)
Test Settings
Setting
Description
5A
51S1O
51S1 Operating Quantity (IA
n
, IB
n
, IC
n
, IMAX
n
, IA
n
R, IB
n
R, IC
n
R,
IMAX
n
R, I1L, 3I2L, 3I0
n
)
a
a
n
= L, 1, and 2 for Line, Circuit Breaker 1, and Circuit Breaker 2, respectively. R suffix selects rms
quantities. For more information on rms, refer to RMS in the Glossary.
3I0L
51S1P
51S1 Overcurrent Pickup (0.25–16 A, secondary)
0.75
51S1C
51S1 Inverse-Time Overcurrent Curve (U1–U5, C1–C5)
U3
51S1TD
51S1 Inverse-Time Overcurrent Time Dial (0.50–15.00)
1.00
51S1RS
51S1 Inverse-Time Overcurrent EM Reset (Y, N)
N
51S1TC
51S1 Torque Control (SEL
OGIC
control equation)
1
I
TEST
M • (51S1P)
=
1.5 • (0.75 A)
=
1.125 A
=
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...