Date Code 20020129
Configuration,
Fast Meter,
and
Fast Operate
Commands
D-9
SEL-387E Instruction Manual
0F
Clear remote bit RB16
2F
Set remote bit RB16
4F
Pulse remote bit RB16
1-byte Reserved
1-byte Checksum
A5E0
Fast Operate
Remote Bit Control
The external device sends the following message to perform a remote bit operation (set, clear,
pulse):
Data Description
A5E0 Command
06 Message
length
1-byte
Operate code (0-F, 20-2F, 40-4F for remote bit clear, set or pulse)
1-byte
Operate validation: 4 * operate code + 1
1-byte Checksum
Remote bit set and clear operations are latched by the relay. Remote bit pulse operations assert
the remote bit for one processing interval.
A5E3
Fast Operate
Breaker Control
The external device sends the following message to perform a fast breaker open/close of
breakers 1 through 4:
Data Description
A5E3 Command
06 Message
length
1-byte
Operate code (hex 31-33 open, hex 11-13 close breakers 1 through 3)
1-byte
Operate validation: 4 * operate code + 1
1-byte Checksum
A5CD
Fast Operate
Reset Definition Block
In response to an A5CD request, the relay sends the configuration block for the
Fast Operate
Reset message
Data Description
A5CD Command
0E Message
length
01
The number of
Fast Operate
reset codes supported
1-byte
Reserved for future use
Per
Fast Operate
reset code, repeat:
00
Fast Operate
reset code (e.g., "00" for target reset)
54415220520000
Fast
Operate
reset description string (e.g., "TAR R")
1-byte Checksum
A5ED
Fast Operate
Reset Command
The
Fast Operate
Reset commands take the following form: