D-2
Configuration,
Fast Meter,
and
Fast Operate
Commands
Date Code 20020129
SEL-387E Instruction Manual
M
ESSAGE
D
EFINITIONS
A5C0 Relay Definition Block
In response to the A5C0 request, the relay sends the following block:
Data Description
A5C0 Command
40
Message length (64 bytes)
02
Support SEL and LMD protocols
03 Support
Fast Meter
, Fast Demand, and Fast Peak
05
Status flag commands supported: Warn, Fail, Group, or Settings change
A5C1
Fast Meter
configuration
A5D1
Fast Meter
message
A5C2
Fast Demand configuration
A5D2
Fast Demand message
A5C3
Fast Peak configuration
A5D3
Fast Peak message
0002
Self-test warning bit
5354410D0000 (STA<CR>) Check status
0003
Self-test failure bit
5354410D0000 (STA<CR>) Check status
0004
Settings change bit
A5C100000000
Reconfigure
Fast Meter
on settings change
0004
Settings change bit
53484F0D0000 (SHO<CR>) Check the settings
0004
53484F20470D (SHO G<CR>) Check the Group settings
0300
SEL protocol has
Fast Operate
0301
LMD protocol has
Fast Operate
00 Reserved
1-byte Checksum
A5C1
Fast Meter
Configuration Block
In response to the A5C1 request, the relay sends the following block:
Data Description
A5C1
Fast Meter
command
E0
Message length (224 bytes)
01
One status flag byte
01
Scale factors in configuration message
05
# scale factors
0D
# analog input channels
02
# samples per channel
32
# digital banks (50 bytes)
04
# calculation blocks
0004
Analog channel data offset
0038
Time stamp offset (56 bytes)