Date Code 20020215
Inputs, Outputs, Timers, and Other Control Logic
7-7
SEL-351R Instruction Manual
ON/OFF/MOMENTARY Switch
The local bit LBn:
is in either the ON (LBn = logical 1) or OFF (LBn = logical 0) position
or
is in the OFF (LBn = logical 0) position and pulses to the MOMENTARY (LBn = logical 1)
position for one processing interval (1/4 cycle).
Figure 7.6: Local Control Switch Configured as an ON/OFF/MOMENTARY Switch
Table 7.2: Correspondence Between Local Control Switch Types
and Required Label Settings
Local Switch Type
Label NLBn
Label CLBn
Label SLBn
Label PLBn
ON/OFF
X X X
OFF/MOMENTARY X
X
X
ON/OFF/MOMENTARY
X X X X
Disable local control switches by “nulling out” all the label settings for that switch (see
Section 9: Setting the SEL-351R Recloser Control
). The local bit associated with this disabled
local control switch is then fixed at logical 0.