8.22
SEL-351A Relay
Instruction Manual
Date Code 20080213
Breaker Monitor and Metering
Demand Metering
Figure 8.12
Voltage V
S
Applied to Series RC Circuit
In the analogy:
Voltage V
S
in
corresponds to the step current input in
(top).
Voltage V
C
corresponds to the
response of the thermal demand meter in
(middle).
If voltage V
S
in
has been at zero (V
S
= 0.0 per unit) for some
time, voltage V
C
across the capacitor in
is also at zero (V
C
= 0.0
per unit). If voltage V
S
is suddenly stepped up to some constant value (V
S
=
1.0 per unit), voltage V
C
across the capacitor starts to rise toward the 1.0 per
unit value. This voltage rise across the capacitor is analogous to the response
of the thermal demand meter in
(middle) to the step current input
(top).
In general, as voltage V
C
across the capacitor in
cannot change
instantaneously, the thermal demand meter response is not immediate either
for the increasing or decreasing applied instantaneous current. The thermal
demand meter response time is based on the demand meter time constant
setting DMTC (see
). Note in
, the thermal demand meter
response (middle) is at 90 percent (0.9 per unit) of full applied value (1.0 per
unit) after a time period equal to setting DMTC = 15 minutes, referenced to
when the step current input is first applied.
The SEL-351A updates thermal demand values approximately every
two seconds.
Rolling Demand Meter Response (EDEM = ROL)
The response of the rolling demand meter in
(bottom) to the step
current input (top) is calculated with a sliding time-window arithmetic average
calculation. The width of the sliding time-window is equal to the demand
meter time constant setting DMTC (see
). Note in
, the
rolling demand meter response (bottom) is at 100 percent (1.0 per unit) of full
applied value (1.0 per unit) after a time period equal to setting DMTC = 15
minutes, referenced to when the step current input is first applied.
The rolling demand meter integrates the applied signal (e.g., step current)
input in 5-minute intervals. The integration is performed approximately every
2 seconds. The average value for an integrated 5-minute interval is derived and
stored as a 5-minute total. The rolling demand meter then averages a number
of the 5-minute totals to produce the rolling demand meter response. In the
example, the rolling demand meter averages the three latest 5-
minute totals because setting DMTC = 15 (15/5 = 3). The rolling demand
meter response is updated every 5 minutes, after a new 5-minute total is
calculated.
The following is a step-by-step calculation of the rolling demand response
example in
(bottom).
V
S
V
C
+
+
—
—
R
C
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...