Setting Negative-Sequence Overcurrent Elements
F-1
SEL-351 Instruction Manual
APPENDIX F: SETTING NEGATIVE-SEQUENCE
OVERCURRENT ELEMENTS
S
ETTING
N
EGATIVE
-S
EQUENCE
D
EFINITE
-T
IME
O
VERCURRENT
E
LEMENTS
Negative-sequence instantaneous overcurrent elements 50Q1 through 50Q6 and 67Q1
through 67Q4 should not be set to trip directly
. This is because negative-sequence current can
transiently appear when a circuit breaker is closed and balanced load current suddenly appears.
To avoid tripping for this transient condition, use negative-sequence definite-time overcurrent
elements 67Q1T through 67Q4T with at least 1.5 cycles of time delay (transient condition lasts
less than 1.5 cycles). For example, make time delay setting:
67Q1D = 1.50
for negative-sequence definite-time overcurrent element 67Q1T. Refer to Figures 3.12 and 3.13
for more information on negative-sequence instantaneous and definite-time overcurrent elements.
Negative-sequence instantaneous overcurrent elements 50Q5 and 50Q6 do not have associated
timers (compare Figure 3.13 to Figure 3.12). If 50Q5 or 50Q6 need to be used for tripping, run
them though SEL
OGIC
®
Control Equation variable timers (see Figures 7.25 and 7.26) and use the
outputs of the timers for tripping.
Continue reading in
Coordinating Negative-Sequence Overcurrent Elements
in this appendix for
guidelines on coordinating negative-sequence definite-time overcurrent elements and a following
coordination example. The coordination example uses time-overcurrent elements, but the same
principles can be applied to definite-time overcurrent elements.
S
ETTING
N
EGATIVE
-S
EQUENCE
T
IME
-O
VERCURRENT
E
LEMENTS
Negative-sequence time-overcurrent element 51QT should not be set to trip directly when it is
set with a low time-dial setting
51QTD,
that results in curve times below 3 cycles
(see curves in
Figures 9.1 through 9.10 in
Section 9: Setting the Relay
). This is because negative-sequence
current can transiently appear when a circuit breaker is closed and balanced load current suddenly
appears. Refer to Figure 3.20 for more information on negative-sequence time-overcurrent element
51QT.
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...