6-8
Close and Reclose Logic
Date Code 20001006
SEL-351 Instruction Manual
Settings and General Operation
Figure 6.2 contains the following SEL
OGIC
Control Equation setting:
79CLS
(reclose supervision conditions – checked after reclosing relay open interval time-
out)
and setting:
79CLSD (Reclose Supervision Limit Time)
See the settings sheets at the end of
Section 9: Setting the Relay
for setting ranges.
For Most Applications (Top of Figure 6.2)
For most applications, the Reclose Supervision Limit Time setting should be set to zero cycles:
79CLSD = 0.00
With this setting, the logic in the top of Figure 6.2 is operative. When an open interval times out,
the SEL
OGIC
Control Equation reclose supervision setting 79CLS is checked just once.
If 79CLS is asserted to logical 1 at the instant of an open interval time-out, then the now-qualified
open interval time-out will propagate onto the final close logic in Figure 6.1 to automatically
reclose the circuit breaker.
If 79CLS is deasserted to logical 0 at the instant of an open interval time-out, the following occurs:
•
No automatic reclosing takes place.
•
Relay Word bit RCSF (Reclose Supervision Failure indication) asserts to logical 1 for
one processing interval.
•
The reclosing relay is driven to the Lockout State.
See
Factory Settings Example
and
Additional Settings Example 1
that follow in this subsection.
For A Few, Unique Applications (Bottom of Figure 6.2 and Figure 6.3)
For a few unique applications, the Reclose Supervision Limit Time setting is not set equal to zero
cycles:
e.g., 79CLSD = 60.00
With this setting, the logic in the bottom of Figure 6.2 is operative. When an open interval times
out, the SEL
OGIC
Control Equation reclose supervision setting 79CLS is then checked for a time
window equal to setting 79CLSD.
If 79CLS asserts to logical 1 at any time during this 79CLSD time window, then the now-qualified
open interval time-out will propagate onto the final close logic in Figure 6.1 to automatically
reclose the circuit breaker.
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...