5-8
Trip and Target Logic
Date Code 20001006
SEL-351 Instruction Manual
Figure 5.3: Three-Pole Open Logic (Top) and Switch-Onto-Fault Logic (Bottom)
Three-Pole Open Logic
Three-pole open (3PO) logic is the top half of Figure 5.3. It is not affected by enable setting
ESOTF (see Settings Sheet 1 of 18 in
Section 9: Setting the Relay
).
The open circuit breaker condition is determined from the combination of:
•
Circuit breaker status (52A)
•
Load current condition (50L)
If the circuit breaker is open (52A = logical 0) and current is below phase pickup 50LP
(50L = logical 0), then the three-pole open (3PO) condition is true:
3PO = logical 1
(circuit breaker open)
The 3POD dropout time qualifies circuit breaker closure, whether detected by circuit breaker
status (52A) or load current level (50L). When the circuit breaker is closed:
3PO = logical 0
(circuit breaker closed)
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...