7.10
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Inputs, Outputs, Timers, and Other Control Logic
Remote Control Switches
Remote Control Switches
Remote control switches are operated via the serial communications port only
(see
CON Command (Control Remote Bit) on page 10.38
The switch representation in this figure is derived from the standard: Graphics
Symbols for Electrical and Electronics Diagrams IEEE Std 315-1975, CSA Z99-1975,
ANSI Y32.2-1975, 4.11 Combination Locking and Nonlocking Switch, Item 4.11.1.
Figure 7.10
Remote Control Switches Drive Remote Bits RB1–RB16
The outputs of the remote control switches in
RB
n
(
n
= 1 to 16), called remote bits. Use these remote bits in SEL
OGIC
control equations.
Any given remote control switch can be put in one of the following three
positions:
➤
ON (logical 1)
➤
OFF (logical 0)
➤
MOMENTARY (logical 1 for one processing interval)
Remote Bit
Application Ideas
With SEL
OGIC
control equations, the remote bits can be used in applications
similar to those that local bits are used in (see preceding local control switch
discussion).
Also, remote bits can be used much as optoisolated inputs are used in
operating latch control switches (see discussion following
). Pulse
(momentarily operate) the remote bits for this application.
Remote Bit States
Not Retained When
Power Is Lost
The states of the remote bits (Relay Word bits RB1–RB16) are not retained if
power to the relay is lost and then restored. The remote control switches
always come back in the OFF position (corresponding remote bit is deasserted
to logical 0) when power is restored to the relay.
Remote Bit States
Retained When
Settings Changed or
Active Setting Group
Changed
The state of each remote bit (Relay Word bits RB1–RB16) is retained if relay
settings are changed (for the active setting group or one of the other setting
groups) or the active setting group is changed. If a remote control switch is in
the ON position (corresponding remote bit is asserted to logical 1) before a
setting change or an active setting group change, it comes back in the ON
position (corresponding remote bit is still asserted to logical 1) after the
change. If a remote control switch is in the OFF position (corresponding
remote bit is deasserted to logical 0) before a settings change or an active
setting group change, it comes back in the OFF position (corresponding
remote bit is still deasserted to logical 0) after the change.
Logical 1
RBn
(n = 1 through 16)
ON Position
(Maintained Logical 1 Position)
OFF Position
(Maintained Logical 0 Position)
MOMENTARY Position
(Logical 1 for One Processing Interval)
Relay
Word
Bit
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...