
3.33
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Overcurrent, Voltage, Synchronism Check, Frequency, and Power Elements
Synchronism Check Elements
Synchronism Check Elements
Enable the two single-phase synchronism check elements by making the
enable setting:
E25 =
Y
show examples where
synchronism check can be applied. Synchronism check voltage input
VS
is
connected to one side of the circuit breaker, on any desired phase. The other
synchronizing phase (
VA
,
VB
, or
VC
voltage inputs) on the other side of the
circuit breaker is setting selected.
The two synchronism check elements use the same voltage window (to assure
healthy voltage) and slip frequency settings (see
). They have
separate angle settings (see
).
If the voltages are static (voltages not slipping with respect to one another) or
setting TCLOSD = 0.00, the two synchronism check elements operate as
shown in the top of
. The angle settings are checked for
synchronism check closing.
If the voltages are not static (voltages slipping with respect to one another),
the two synchronism check elements operate as shown in the bottom of
. The angle difference is compensated by breaker close time, and
the breaker is ideally closed at a zero degree phase angle difference, to
minimize system shock.
These synchronism check elements are explained in detail in the following
text.
Voltage Input VS
Connected Phase-to-
Phase or Beyond
Delta-Wye
Transformer
Sometimes synchronism check voltage V
S
cannot be in phase with voltage
V
A
, V
B
, or V
C
(wye connected PTs); or V
AB
, V
BC
, or V
CA
(delta-connected
PTs). This happens in applications where voltage input
VS
is connected
➤
Phase-to-phase when using a wye-connected relay
➤
Phase-to-neutral when using a delta-connected relay
➤
Beyond a delta-wye transformer
For such applications requiring V
S
to be at a constant phase angle difference
from any of the possible synchronizing voltages (V
A
, V
B
, or V
C
; V
AB
, V
BC
, or
V
CA
), an angle setting is made with the SYNCP setting (see
Synchronism Check
Elements Settings
NOTE:
If global setting VSCONN =
3V0, the synchronism check elements
are unavailable, and E25 = N is the
only possible setting. See
Delta VS Connection (Global Setting
VSCONN = 3V0) on page 2.14
for
details.
Table 3.11
Synchronism Check Elements Settings and Settings Ranges
Setting
Definition
Range
25VLO
low voltage threshold for
“healthy voltage” window
0.00–150.00 V secondary
(150 V voltage inputs)
0.00–300.00 V secondary
(300 V voltage inputs)
25VHI
high voltage threshold for
“healthy voltage” window
0.00–150.00 V secondary
(150 V voltage inputs)
0.00–300.00 V secondary
(300 V voltage inputs)
25SF
maximum slip frequency
0.005–0.500 Hz
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...