2-12
Specifications
Date Code 20011026
SEL-321/321-1 Instruction Manual
Creating Other Tripping Schemes
Permissive Underreaching Transfer Trip Schemes
Use the POTT logic for the echo keying and Weak-Infeed logic. Program an output contact with
Zone 1 distance elements to key permissive trip.
Direct Underreaching Transfer Trip Schemes
Three-Pole Trip Applications
. Assign an input to DT (Direct Trip). Program this element in
the unconditional trip variable (MTU) to trip the breaker upon assertion of the DT input.
Program an output contact with Zone 1 distance elements to key the communication equipment
to send the direct trip signal when any Zone 1 element asserts.
Single-Pole Trip Applications
. Assign inputs to DTA, DTB, and DTC. Assertion of an input
causes the corresponding trip variable to assert.
Direct Transfer Trip Schemes
Three-Pole Trip Applications
. Assign an input to DT (Direct Trip). Program this element in
the unconditional trip variable to trip the breaker upon assertion of the DT input. Program an
output contact with a tripping element to key the communication equipment to send the direct
trip signal when the relay asserts a tripping signal.
Single-Pole Trip Applications
. Assign inputs to DTA, DTB, and DTC. Assertion of an input
causes the corresponding trip variable to assert.
Figure 2.1 shows the necessary connections between the SEL-321 Relay and the communication
equipment.
Figure 2.1: Signal Connections Between Relay and Communication Equipment
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......