12-10
Standard Event Reports and SER
Date Code 20010625
SEL-311L Instruction Manual
The filters for ac current and voltage and station battery are fixed. You can adjust the
optoisolated input debounce via debounce settings (see Figure 7.1 in
Section 7: Inputs, Outputs,
Timers, and Other Control Logic
).
Raw event reports display one extra cycle of data at the beginning of the report.
Clearing Standard Event Report Buffer
The
HIS C
command clears the event summaries and corresponding standard event reports from
nonvolatile memory. See
Section 10: Line Current Differential Communications and Serial
Port Communications and Commands
for more information on the
HIS
(Event
Summaries/History) command.
Standard Event Report Column Definitions for Backup Protection
Refer to the example event report in Figure 12.4 to view event report columns
(
Note
: Figure 12.4 is on multiple pages). This example event report displays rows of
information each 1/4 cycle and was retrieved with the
EVE B
command.
The columns contain ac current, ac voltage, station dc battery voltage, and directional polarizing
voltage (V1Mem).
Current, Voltage, and Frequency Columns in the Backup Protection Event Report
Table 12.2 summarizes the backup event report current, voltage, and frequency columns.
Table 12.2: Standard Event Report Current, Voltage,
and Frequency Columns (Backup Protection)
Column Heading
Definition
IA
Current measured by channel IA (primary A)
IB
Current measured by channel IB (primary A)
IC
Current measured by channel IC (primary A)
IP
Current measured by channel IP (primary A)
IG
Calculated residual current IG = 3I
0
= IA + IB + IC (primary A)
VA
Voltage measured by channel VA (primary kV)
VB
Voltage measured by channel VB (primary kV)
VC
Voltage measured by channel VC (primary kV)
VS
Voltage measured by channel VS (primary kV)
V1Mem
Positive-sequence memory voltage (primary kV)
FREQ
Frequency of Channel VA
Vdc
Voltage measured at power input terminals Z25 and Z26 (Vdc)
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......