Date Code 20010625
Close and Reclose Logic
6-3
SEL-311L Instruction Manual
If a user wants to supervise the CLOSE command with optoisolated input IN106, the following
addition is made:
CL = CC * IN106
With this setting, the CLOSE command can provide a close only if optoisolated input IN106 is
asserted. This is just one CLOSE command supervision example—many variations and
additional conditions may be incorporated by the user.
Unlatch Close
If the CLOSE Relay Word bit is asserted, it stays asserted until one of the following occurs:
•
The unlatch close condition asserts (ULCL = logical 1).
•
The circuit breaker closes (52A = logical 1).
•
The reclose initiation condition (79RI) makes a rising edge (logical 0 to logical 1)
transition.
•
The Close Failure Timer times out (Relay Word bit CF = 1).
The Close Failure Timer is inoperative if setting CFD = OFF.
Factory Settings Example
The factory settings for the close logic SEL
OGIC
control equation settings are:
52A =
IN101
CL =
CC
ULCL
= TRIP + TRIP87
The factory setting for the Close Failure Timer setting is:
CFD =
60.00
cycles
See the settings sheets at the end of
Section 9: Setting the Relay
for setting ranges.
Set Close
If the Reclosing Relay Open Interval Time-Out logic input at the top of Figure 6.1 is ignored
(reclosing is discussed in detail in a following subsection), then SEL
OGIC
control equation
setting CL is the only logic input that can set the CLOSE Relay Word bit.
In SEL
OGIC
control equation setting CL = CC, Relay Word bit CC asserts for execution of the
CLOSE Command. See
CLO Command (Close Breaker)
in
Section 10: Line Current
Differential Communications and Serial Port Communications and Commands
for more
information on the CLOSE Command.
Unlatch Close
SEL
OGIC
control equation setting ULCL has a default of TRIP + TRIP87. This prevents the
CLOSE Relay Word bit from being asserted any time the TRIP or TRIP87 Relay Word bits are
asserted. See
Trip Logic
in
Section 5: Trip and Target Logic
.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......