5-38
Trip and Target Logic
Date Code 20010625
SEL-311L Instruction Manual
FAULT TYPE Target LEDs
A, B, and C Target LEDs
“A” (Phase A) target LED is illuminated at the rising edge of trip if a protection element causes
the trip and Phase A is involved in the fault (likewise for “B” [Phase B] and “C” [Phase C] target
LEDs).
G Target LED
G target LED is illuminated at the rising edge of trip if ground is involved in the fault.
Zone LEDs
Zone/Level LEDs illuminate for the lowest zone number detected during the fault (M1P, M2P,
M3P, Z1G, Z2G, Z3G, 50P1, 67P1, 67P2, 67P3, 67P4, 67G1, 67G2, 67G3, 67Q1, 67Q2, 67Q3).
87CH FAIL LED
The 87CH FAIL LED illuminates when the relay detects a problem with any active 87L
Communications Channel. See
Section 10: Line Current Differential Communications and
Serial Port Communications and Commands
for more information about the 87CH FAIL LED.
Target Reset/Lamp Test Front-Panel Pushbutton
When the Target Reset/Lamp Test front
-
panel pushbutton is pressed:
v
All front
-
panel LEDs illuminate for one (1) second.
v
All latched target LEDs (target LEDs numbered 2 through 6 and 9 through 15 in
Table 5.1) are extinguished (unlatched).
Other Applications for the Target Reset Function
Refer to the bottom of Figure 5.4. The combination of the TARGET RESET Pushbutton and the
TAR R
(Target Reset) serial port command is available as Relay Word bit TRGTR. Relay Word
bit TRGTR pulses to logical 1 for one processing interval when either the TARGET RESET
Pushbutton is pushed or the
TAR R
(Target Reset) serial port command is executed.
Relay Word bit TRGTR can be used to unlatch logic. For example, refer to the breaker failure
logic in Figure 7.25 in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
. If a
breaker failure trip occurs (SV7T asserts), the occurrence can be displayed on the front panel
with seal-in logic and a rotating default display (see
Rotating Default Display
in
Section 7
and
Section 11
, also):
SV8 = (SV8 + SV7T) * !TRGTR
DP3 = SV8
DP3_1 = BREAKER FAILURE
DP3_0 = (blank)
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......