
5-18
Trip and Target Logic
Date Code 20010625
SEL-311L Instruction Manual
Figure 5.7: Permissive Input Logic Routing to POTT Logic
Also note that SEL
OGIC
control equation setting PT1 in Figure 5.9 is routed to control Relay
Word bit PTRX if enable setting ECOMM = POTT. Relay Word bit PTRX is the permissive trip
receive input into the trip logic in Figure 5.4.
Timer Settings
See
Section 9: Setting the Relay
for setting ranges.
Z3RBD—Zone (Level) 3 Reverse Block Delay
Current-reversal guard timer—typically set at 5 cycles.
EBLKD—Echo Block Delay
Prevents echoing of received PT for settable delay after dropout of local permissive elements in
trip setting TRCOMM—typically set at 10 cycles. Set to OFF to defeat EBLKD.
ETDPU—Echo Time Delay Pickup
Sets minimum time requirement for received PT, before echo begins—typically set at 2 cycles.
Set to OFF for no echo.
EDURD—Echo Duration
Limits echo duration, to prevent channel lockup—typically set at 4.0 cycles.
Logic Outputs
The following logic outputs can be tested by assigning them to output contacts. See
Output
Contacts
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more information
on output contacts.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......