3.19
Date Code 20060320
Instruction Manual
SEL-311C Relay
Distance, Out-of-Step, Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Distance Element Operating Time Curves at Nominal Frequency
Additional Distance
Element Supervision
The SEL-311C uses Relay Word bit VPOLV for positive-sequence memory
supervision of mho and quadrilateral characteristics. VPOLV asserts when the
memorized positive-sequence polarizing voltage is greater than 1 Volt.
Phase and ground distance elements are supervised with Fault Identification
Selection (FIDS) logic. This logic identifies the faulted phase(s) for all faults
involving ground by comparing the angle between I0 and I2. For example,
when FIDS selects A-phase, FSA asserts and enables A phase ground distance
elements and CB-phase distance elements. Distance elements BG, CG, AB,
and CA are blocked.
Zone 1 Extension
. When enabled, this logic modifies the reach of all Zone 1
distance elements by multiplier setting Z1EXTM once all three poles are
closed for Z1EXTD time. All Zone 1 reaches retreat to their set reach when
3PO asserts.
The Zone 1 reaches cannot be extended if any of the following elements are
asserted: M1P–M2P, Z1G–Z2G, 51G, or 51Q.
q
;
w
from
;
e
r
from
;
t
y
;
u
from
;
i
Figure 3.15
Zone 1 Extension Logic
Table 3.4
Zone 1 Settings
Description
Setting
Setting Recommendation
Enable Zone 1 Extension
EZ1EXT
Zone 1 Extension Delay
Z1EXTD
Sets the minimum time the breaker must be
closed before extending the Zone 1 reach.
Zone 1 Extension Multiplier
Z1EXTM
Sets the scalar by which all Zone 1
reaches are multiplied. Z1EXTM times
the Zone 1 distance setting is never set
less than the Zone 1 distance setting or greater
than 90 percent of Zone 2 reach.
Z1P < (Z1EXTM • Z1P) < (0.9 • Z2P) and
Z1MG < (Z1EXTM • ZMG) < (0.9 • Z2MG)
and X1G < (Z1EXTM • X1G) < (0.9 • X2G)
must all be true or the SEL-311C will
not allow the Z1EXTM setting.
EZ1EXT = N
(Setting)
q
51Q
0
Z1EXTD
S
R
Q
Z1X
w
51G
e
M1P
r
Z1G
t
M2P
y
Z2G
u
3PO
Z1X
0
1
X1
(See
e
,
r
, and
i
)
1.0
Z1EXTM
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...