8.22
SEL-311C Relay
Instruction Manual
Date Code 20060320
Breaker Monitor and Metering Functions
Demand Metering
Figure 8.12
Current I
S
Applied to Parallel RC Circuit
In the analogy:
➤
Current I
S
corresponds to the step current input
in
(top).
➤
Voltage V
C
corresponds to
the response of the thermal demand meter in
(middle).
If current I
S
in
has been at zero (I
S
= 0.0 per unit) for some time,
voltage V
C
across the capacitor in
is also at zero (V
C
= 0.0 per
unit). If current I
S
is suddenly stepped up to some constant value (I
S
= 1.0 per
unit), voltage V
C
across the capacitor starts to rise toward the 1.0 per unit
value. This voltage rise across the capacitor is analogous to the response of the
thermal demand meter in
(middle) to the step current input (top).
In general, just as voltage V
C
change instantaneously, the thermal demand meter response cannot change
instantaneously for increasing or decreasing current. The thermal demand
meter response time is based on the demand meter time constant setting
DMTC (see
). Note in
, the thermal demand meter
response (middle) is at 90 percent (0.9 per unit) of full applied value (1.0 per
unit) after a time period equal to setting DMTC = 15 minutes, referenced to
when the step current input is first applied.
The SEL-311C updates thermal demand values approximately every two
seconds.
Rolling Demand Meter Response (EDEM = ROL)
The response of the rolling demand meter in
(bottom) to the step
current input (top) is calculated with a sliding time-window arithmetic average
calculation. The width of the sliding time-window is equal to the demand
meter time constant setting DMTC (see
). Note in
, the
rolling demand meter response (bottom) is at 100 percent (1.0 per unit) of full
applied value (1.0 per unit) after a time period equal to setting DMTC = 15
minutes, referenced to when the step current input is first applied.
The rolling demand meter integrates the applied signal (e.g., step current)
input in five-minute intervals. The integration is performed approximately
every two seconds. The average value for an integrated five-minute interval is
derived and stored as a five-minute total. The rolling demand meter then
averages a number of the five-minute totals to produce the rolling demand
meter response. In the
example, the rolling demand meter
averages the three latest five-minute totals because setting DMTC = 15 (15/5
= 3). The rolling demand meter response is updated every five minutes, after a
new five-minute total is calculated.
V
C
+
—
R
C
I
S
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...