7-46
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
Mnemonic
Display
Description
MVRAPO M V R A O P K
= x . x x x A peak megavars out
MVRBDO M V R B O D E M = x . x x x B demand megavars out
MVRBPO
M V R B O P K
= x . x x x B peak megavars out
MVRCDO M V R C O D E M = x . x x x C demand megavars out
MVRCPO
M V R C O P K
= x . x x x C peak megavars out
MVR3DO M V R 3 O D E M = x . x x x three-phase demand megavars out
MVR3PO
M V R 3 O P K
= x . x x x three-phase peak megavars out
MWHAI
MW h A I N =
x x . x x x A megawatt-hours in
MWHAO
MW h A O U T = x x . x x x A megawatt-hours out
MWHBI
MW h B I N =
x x . x x x B megawatt-hours in
MWHBO
MW h B O U T = x x . x x x B megawatt-hours out
MWHCI
MW h C I N =
x x . x x x C megawatt-hours in
MWHCO
MW h C O U T = x x . x x x C megawatt-hours out
MWH3I
MW h 3 I N =
x x . x x x three-phase megawatt-hours in
MWH3O
MW h 3 O U T = x x . x x x three-phase megawatt-hours out
MVRHAI
M V A R h A
I = x x . x x x A megavar-hours in
MVRHAO M V A R h A
O = x x . x x x A megavar-hours out
MVRHBI
M V A R h B
I = x x . x x x B megavar-hours in
MVRHBO M V A R h B
O = x x . x x x B megavar-hours out
MVRHCI
M V A R h C
I = x x . x x x C megavar-hours in
MVRHCO M V A R h C
O = x x . x x x C megavar-hours out
MVRH3I M V A R h 3
I = x x . x x x three-phase megavar-hours in
MVRH3O M V A R h 3
O = x x . x x x three-phase megavar-hours out
To program a display point to display one of the metering quantities above, first enter the two-
character sequence “::” (double colon) followed by the name of the desired metering quantity
(e.g., IA, VA, MW3, etc.).
If the display point setting does not match the format correctly, the relay will display the setting
text string as it was actually entered, without substituting the metering value.
Displaying Metering Values Example
This example demonstrates use of the rotating display to show metering quantities automatically
on the rotating default display. This example will set the MW3, MVAR3, PF3, and FREQ to
display in the rotating default display.
Set the following:
SET T
SET L
DP1_0 = ::MW3
DP1 = 0
DP2_0 = ::MVAR3
DP2 = 0
DP3_0 = ::PF3
DP3 = 0
DP4_0 = ::FREQ
DP4 = 0
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......